Safety first
Gas heater: the gas valve, burners, ignition, flame sensing, venting and anything behind the cabinet panels are for a qualified gas technician. Never jumper or bypass a safety switch or limit. If you smell gas, shut off the gas supply, do not touch electrical switches, leave the area and call your gas company from outside.
Jump to a code
| Code | What it means |
|---|---|
| SERVICE HEATER | Fault in the heater or its controls |
| HEATING blinking | The heater wants to heat but is not firing |
| LED 1 flash | Air flow fault |
| LED 2 flashes | Flame with no call for heat |
| LED 3 flashes | Ignition lockout |
| AGS or HLS LED | Automatic gas shutoff or high limit switch open |
| PS LED | Water pressure switch open |
| AFS LED | Air flow switch open |
| THERMISTOR LED | Water temperature thermistor fault |
| SFS LED | Stack flue sensor / excessive stack flue temperature |
| E05 / E06 | Stack flue sensor error (part of the SFS chart) |
| SERVICE SYSTEM | Insufficient water flow to the heater |
| ERR PS | Water pressure switch open: no water flow through the heater |
| ERR HLS | High temperature limit switch open: water after the 1st pass through the heat exchanger above 135°F (57°C) |
| ERR AFS | Air flow switch open: blower off or air flow restricted |
| ERR IGN | Ignition control module could not ignite the heater |
| ERR AGS | Automatic gas shutoff: water after the 2nd pass through the heat exchanger above 140°F (60°C) |
| ERR SFS | Excessive stack flue temperature: stack flue above 480°F (249°C) |
| E05 | Open stack flue sensor |
| E06 | Shorted stack flue sensor |
| E01 | Open water temperature sensor |
| 126 | Shorted water temperature sensor |
SERVICE HEATER Fault in the heater or its controls
Display shows: SERVICE HEATER light on
What it means
Fault in the heater or its controls.
Common causes
- Heater or control fault (see red diagnostic LEDs on the back of the control board)
What to check, in order
- Shut down the heater (turn off gas to the appliance)
- Get a qualified service technician to inspect the system.
- Technician: check the red diagnostic LEDs (AGS, AFS, SFS, HLS, PS) and follow those charts
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 36. maker's manual (PDF) The same code is also in 1 other manual or revision.
HEATING blinking The heater wants to heat but is not firing
Display shows: HEATING light blinking
What it means
The heater wants to heat but is not firing. If it is on yet the burner stays off, one of the service lights should light.
Common causes
- Call for heat without firing
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving burners is a job for a qualified technician.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 36. maker's manual (PDF) The same code is also in 1 other manual or revision.
LED 1 flash Air flow fault
Display shows: Ignition module diagnostic LED: 1 flash
What it means
Air flow fault.
Common causes
- Air flow fault
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 36. maker's manual (PDF) The same code is also in 1 other manual or revision.
LED 2 flashes Flame with no call for heat
Display shows: Ignition module diagnostic LED: 2 flashes
What it means
Flame with no call for heat.
Common causes
- Flame present with no call for heat
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 36. maker's manual (PDF) The same code is also in 1 other manual or revision.
LED 3 flashes Ignition lockout
Display shows: Ignition module diagnostic LED: 3 flashes
What it means
Ignition lockout.
Common causes
- Ignition lockout
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 36. maker's manual (PDF) The same code is also in 1 other manual or revision.
AGS or HLS LED Automatic gas shutoff or high limit switch open
Display shows: AGS or HLS "on" (red LED on back of control board)
What it means
Automatic gas shutoff or high limit switch open.
Common causes
- Water flow below the heater minimum
- Inlet water above 104°F (40°C) (thermistor or control board)
- Failed high limit switch or automatic gas shutoff
- Internal bypass, thermal governor or heat exchanger blockage
What to check, in order
- Service the pump and filter to restore flow; verify the pressure switch
- If inlet water is above 104°F (40°C) replace the thermistor or control board
- Otherwise replace the HLS or AGS
- If it persists, check the internal bypass valve, thermal governor and heat exchanger
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 43. maker's manual (PDF) The same code is also in 1 other manual or revision.
PS LED Water pressure switch open
Display shows: PS "on" (red LED on back of control board)
What it means
Water pressure switch open.
Common causes
- Low water flow
- Pressure switch out of adjustment
- Wiring, blocked pressure tap or failed switch
What to check, in order
- Service pump and filter to restore flow
- Adjust the water pressure switch to close with the pump running and open with the pump off
- Check wiring and pressure tap; replace the pressure switch
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 43. maker's manual (PDF) The same code is also in 1 other manual or revision.
AFS LED Air flow switch open
Display shows: AFS "on" (red LED on back of control board)
What it means
Air flow switch open.
Common causes
- Blocked blower intake, heat exchanger or exhaust
- Exhaust too long
- AFS wiring, pressure taps or tubing
- Failed air flow switch
- Blower or ignition control module failure
- Wiring BM/F1 or 24VAC/IND
What to check, in order
- Blower runs: clear blockages, check exhaust length, AFS wiring, taps and vinyl tubing; replace the AFS, then the blower
- Blower off: check line voltage at blower connector pins 1 and 3 on ignition try (present = replace blower)
- Check 24VAC/GND and IND wiring at the ignition control module; correct wiring or replace the control board
- Check BM and F1 wiring; jumper F1-F2 test per chart; replace the blower or ignition control module
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 43. maker's manual (PDF) The same code is also in 1 other manual or revision.
THERMISTOR LED Water temperature thermistor fault
Display shows: THERMISTOR "on" (red LED on back of control board)
What it means
Water temperature thermistor fault.
Common causes
- Thermistor wiring
- Failed thermistor
What to check, in order
- Check thermistor wiring; if OK replace the thermistor
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 43. maker's manual (PDF) The same code is also in 1 other manual or revision.
SFS LED Stack flue sensor / excessive stack flue temperature
Display shows: SFS "on" (red LED on back of control board)
What it means
Stack flue sensor / excessive stack flue temperature.
Common causes
- Thermal regulator not opening at 120°F (49°C) or not seating
- Heat exchanger leaks, liming, soot or low flow
- Fuel supply pressure/volume
- Stack flue sensor open or shorted
- Harness or J3/J6 connector fault
What to check, in order
- Exhaust rises to 450-500° within 3-5 min: inspect the thermal regulator and the heat exchanger.
- Check fuel supply pressure and volume
- Check sensor resistance (3.5-4.0 megohms); replace the stack flue sensor if open or shorted
- Check harness continuity; clean/tighten J3 and J6 pins
- Then replace the membrane pad / control board per chart and retry
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 44. maker's manual (PDF) The same code is also in 1 other manual or revision.
E05 / E06 Stack flue sensor error (part of the SFS chart)
Display shows: E05 or E06 on the digital temperature display
What it means
Stack flue sensor error (part of the SFS chart).
Common causes
- Stack flue sensor circuit fault
What to check, in order
- Follow the SFS chart: replace membrane pad and/or control board as directed (HD vs Basic panel), reset power and retry
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 44. maker's manual (PDF) The same code is also in 1 other manual or revision.
SERVICE SYSTEM Insufficient water flow to the heater
Display shows: SERVICE SYSTEM light on
What it means
Insufficient water flow to the heater.
Common causes
- Dirty filter or skimmers
- Pump off or flow below minimum (175/200: 20 gpm (76 L/min), 250: 25, 300: 30, 400: 40)
- Water pressure switch out of adjustment or failed
What to check, in order
- Clean the filter/skimmers (backwash if needed); service the pump
- With the pump running, adjust the water pressure switch until the light goes out, and confirm it comes on with the pump off
- Check water pressure is within the switch range (0-5 psig); otherwise fit a flow switch set above minimum flow
- Check switch wiring and port; replace the pressure switch
- If the light stays lit once the filter is serviced, have a qualified service technician inspect the system.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 400, MasterTemp 125
Source: the Pentair installation and user's guide (P/N 472592 REV. M 1/2015), page 36. maker's manual (PDF) The same code is also in 1 other manual or revision.
ERR PS Water pressure switch open: no water flow through the heater
What it means
Water pressure switch open: no water flow through the heater. Clears and operation resumes when flow is established.
Common causes
- No water flow thru heater
- Flow below the heater minimum
- Pressure switch wiring, blocked pressure tap or failed switch
- Pressure switch out of adjustment
What to check, in order
- Clean the filter/skimmers (backwash if needed) and service the pump to restore flow
- Check wiring and that the pressure tap is not blocked; replace the pressure switch
- Adjust the water pressure switch to close with the pump running and open with the pump off
- If the message stays after servicing the filter, have a qualified service technician check the system
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
ERR HLS High temperature limit switch open: water after the 1st pass through the heat exchanger above 135°F (57°C)
What it means
High temperature limit switch open: water after the 1st pass through the heat exchanger above 135°F (57°C); clears when it drops below 135°F (57°C).
Common causes
- Water after the 1st pass through the heat exchanger above 135°F (57°C)
- Low water flow
- Inlet water above 104°F (40°C) (thermistor or control board)
- Failed high limit switch
- Internal bypass, thermal governor or heat exchanger blockage
What to check, in order
- Restore flow above the minimum (service pump and filter, then check the pressure switch)
- If inlet water is above 104°F (40°C), replace the thermistor or control board
- Otherwise replace the high limit switch
- If it persists, check the internal bypass valve, thermal governor and heat exchanger for blockage
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
ERR AFS Air flow switch open: blower off or air flow restricted
What it means
Air flow switch open: blower off or air flow restricted. If air flow returns within 60 s the heater resumes; otherwise press HEATER OFF to clear.
Common causes
- Blower not on
- Air flow through the heater restricted
- Wiring or AFS tubing fault
- Failed air flow switch
- Failed blower or ignition control module
What to check, in order
- Blower runs: check blower intake, heat exchanger and exhaust for blockage and exhaust length; check AFS wiring and pressure taps; check vinyl tubing to AFS and blower; replace the AFS; then the blower
- Blower does not run: check line voltage at blower connector pins 1 and 3 on ignition try (present = replace blower)
- Check 24VAC between 24VAC and GND on the ignition control module and the IND wire; correct wiring between module and control board or replace the control board
- Check BM and F1 wiring at the terminal strip; jumper F1-F2 test per chart, then replace the blower or ignition control module
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
ERR IGN Ignition control module could not ignite the heater
What it means
Ignition control module could not ignite the heater. Press HEATER OFF to clear.
Common causes
- Failed ignition
- HSI igniter fault
- Low gas pressure or flow
- Gas valve fault
- Ignition control module or control board fault
- Wiring between boards
What to check, in order
- Verify HSI igniter connection, that it is not broken, and flame current
- Check igniter voltage: none = replace ignition control module (on 120V check the igniter for 240V damage)
- Check gas pressure; if low enlarge the gas line, replace the regulator and/or meter
- Blower not on: replace the control board
- Check gas is open to the valve and for 24VAC at the gas valve during ignition; replace the gas valve with an identical part if powered
- Check 24VAC TH/GND, VAL/GND and GAS terminals per chart; fix wiring or replace the ignition control module/control board
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
ERR AGS Automatic gas shutoff: water after the 2nd pass through the heat exchanger above 140°F (60°C)
What it means
Automatic gas shutoff: water after the 2nd pass through the heat exchanger above 140°F (60°C); front panel buttons disabled, cycle power to reset.
Common causes
- Water after the 2nd pass above 140°F (60°C)
- Low water flow
- Inlet water above 104°F (40°C)
- Failed automatic gas shutoff switch
What to check, in order
- Restore flow above the minimum
- If inlet water is above 104°F (40°C), replace the thermistor or control board
- Otherwise replace the automatic gas shutoff (AGS)
- If it persists, check the internal bypass valve, thermal governor and heat exchanger for blockage
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
ERR SFS Excessive stack flue temperature: stack flue above 480°F (249°C)
What it means
Excessive stack flue temperature: stack flue above 480°F (249°C); front panel buttons disabled, cycle power to reset.
Common causes
- Stack flue above 480°F (249°C)
- Thermal regulator not opening at 120°F (49°C) or not seating
- Heat exchanger leaks, liming, soot or low flow
- Fuel supply pressure/volume
- Stack flue sensor or wiring fault
What to check, in order
- Exhaust rising to 450-500° in 3-5 min: make sure the thermal regulator opens at 120°F (49°C), then look for low flow, leaks, liming or soot in the heat exchanger.
- Check fuel supply pressure and volume
- Check the stack flue sensor resistance (3.5-4.0 megohms); replace if open or shorted
- Check harness continuity between control board and probe; clean/tighten J3 and J6 pins
- Then replace the heater control board / membrane pad per chart and retry
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
E05 Open stack flue sensor
What it means
Open stack flue sensor.
Common causes
- Stack flue sensor open
What to check, in order
- Follow the SFS diagram: check sensor resistance (3.5-4.0 megohms), wiring and J3/J6 connectors; replace the sensor or control board as the manufacturer's chart directs
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
E06 Shorted stack flue sensor
What it means
Shorted stack flue sensor; front panel buttons disabled, cycle power to reset.
Common causes
- Stack flue sensor shorted
What to check, in order
- Follow the SFS diagram: check sensor resistance (3.5-4.0 megohms), wiring and J3/J6 connectors; replace the sensor or control board as the manufacturer's chart directs
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
E01 Open water temperature sensor
What it means
Open water temperature sensor; press HEATER OFF to clear.
Common causes
- Water temperature sensor open
- Thermistor wiring
What to check, in order
- Check thermistor wiring; if OK replace the thermistor
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
126 Shorted water temperature sensor
What it means
Shorted water temperature sensor.
Common causes
- Water temperature sensor shorted
- Thermistor wiring
What to check, in order
- Check thermistor wiring; if OK replace the thermistor
When to call a pro: The manufacturer's main advice for this code is to have a qualified service technician check the unit.
Applies to: MasterTemp 125, MasterTemp 175, MasterTemp 200, MasterTemp 250, MasterTemp 300, MasterTemp 333, MasterTemp 400
Source: the Pentair installation and user's guide (P/N 472592 REV. Q 7/30/23), page 48. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
Blue knows every code and the manual for your exact model
Ask Blue free in the Pool AI app: tell Blue the code and your model, and get the steps for your equipment.
Ask Blue freePool company? Give your techs Blue: every code, every manual and your customers' equipment in one app.
Questions
What does Pentair code ERR PS mean on MasterTemp heaters?
Water pressure switch open: no water flow through the heater. Clears and operation resumes when flow is established. First check: Clean the filter/skimmers (backwash if needed) and service the pump to restore flow.
What does Pentair code ERR HLS mean on MasterTemp heaters?
High temperature limit switch open: water after the 1st pass through the heat exchanger above 135°F (57°C); clears when it drops below 135°F (57°C). First check: Restore flow above the minimum (service pump and filter, then check the pressure switch).
What does Pentair code ERR AFS mean on MasterTemp heaters?
Air flow switch open: blower off or air flow restricted. If air flow returns within 60 s the heater resumes; otherwise press HEATER OFF to clear. First check: Blower runs: check blower intake, heat exchanger and exhaust for blockage and exhaust length; check AFS wiring and pressure taps; check vinyl tubing to AFS and blower; replace the AFS; then the blower.
What does Pentair code ERR IGN mean on MasterTemp heaters?
Ignition control module could not ignite the heater. Press HEATER OFF to clear. First check: Verify HSI igniter connection, that it is not broken, and flame current.
What does Pentair code ERR AGS mean on MasterTemp heaters?
Automatic gas shutoff: water after the 2nd pass through the heat exchanger above 140°F (60°C); front panel buttons disabled, cycle power to reset. First check: Restore flow above the minimum.
Related
- Pentair Max-E-Therm heaters (Sta-Rite)
- Pentair ETi 250 & ETi 400 heaters
- Pentair PowerMax commercial heaters
- Pentair MiniMax 100 heaters
- All Pentair error codes
- All pool equipment error codes
General information from the manufacturers' manuals, written in our own words. Pool AI is not affiliated with or endorsed by the brands named here; brand and model names belong to their owners. Always follow the manual for your exact model and your local codes. Work on gas, high voltage and refrigerant only by qualified, licensed people. Updated 2026-11-23.