Raypak MVB commercial heaters & boiler (504A–2004A) error codes

23 codes for 504A, 754A, 1104A, 1504A, 2004A: what each one means, what to check first, and when to call a pro.

Safety first

Gas heater: the gas valve, burners, ignition, flame sensing, venting and anything behind the cabinet panels are for a qualified gas technician. Never jumper or bypass a safety switch or limit. If you smell gas, shut off the gas supply, do not touch electrical switches, leave the area and call your gas company from outside.

Jump to a code

CodeWhat it means
OUTLET SENError display item: outlet water sensor
LIMIT SENError display item: high limit sensor
INLET SENError display item: inlet sensor
GAS PRESSError display item: gas pressure
IGNITIONError display item: ignition
LIMIT TRIPBoiler temperature tripped the high limit
FLAMEFalse flame detected
ID CARDIdentity card error
IGN CTRLInternal control fault
DELTA TTemperature difference between inlet and outlet exceeded the setpoint
LOW 24VACLow 24 VAC power
BLOW SPEEDBlower speed out of range
PIM red LED offNormal operation
PIM red LED steady on, green power LED offID Card Fault
PIM red LED steady onInternal Control Failure
PIM red LED 2 flashesFalse Flame Error
PIM red LED 3 flashesIgnition Lockout Fault
PIM red LED 5 flashesLow Voltage Fault: 24 VAC input must be above 18.0 VAC
PIM red LED 7 flashesHi-Limit Fault
PIM red LED 8 flashesSensor Fault
PIM red LED 13 flashesHi-Temperature Delta Fault
PIM red LED 14 flashesFt-Bus Communications Fault
PIM red LED 15 flashesSafety circuit open

OUTLET SEN Error display item: outlet water sensor

What it means

Error display item: outlet water sensor.

Common causes

What to check, in order

  1. Inspect the outlet water sensor and its wiring.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

LIMIT SEN Error display item: high limit sensor

What it means

Error display item: high limit sensor.

Common causes

What to check, in order

  1. Inspect the high limit sensor and its wiring.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

INLET SEN Error display item: inlet sensor

What it means

Error display item: inlet sensor.

Common causes

What to check, in order

  1. Check the inlet sensor and its wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

GAS PRESS Error display item: gas pressure

What it means

Error display item: gas pressure.

What to check, in order

  1. Check PIM wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or gas supply and pressure is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

IGNITION Error display item: ignition

What it means

Error display item: ignition.

What to check, in order

  1. Reset the control: push and release the RESET button

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

LIMIT TRIP Boiler temperature tripped the high limit

What it means

Boiler temperature tripped the high limit.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

FLAME False flame detected

What it means

False flame detected.

Common causes

What to check, in order

  1. Shut off the gas supply
  2. Recycle power

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

ID CARD Identity card error

What it means

Identity card error.

What to check, in order

  1. Check the ID card and wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

Ask Blue freeGive your techs Blue

IGN CTRL Internal control fault

What it means

Internal control fault.

Common causes

What to check, in order

  1. Reset power
  2. Replace the control

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

DELTA T Temperature difference between inlet and outlet exceeded the setpoint

What it means

Temperature difference between inlet and outlet exceeded the setpoint.

Common causes

What to check, in order

  1. Check water flow

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

LOW 24VAC Low 24 VAC power

What it means

Low 24 VAC power.

Common causes

What to check, in order

  1. Check power supply wiring and transformer

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage, wiring or electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

BLOW SPEED Blower speed out of range

What it means

Blower speed out of range.

Common causes

What to check, in order

  1. Check blower wiring and blower

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED off Normal operation

Display shows: Off

What it means

Normal operation.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED steady on, green power LED off ID Card Fault

Display shows: Red LED steady ON, Green Power LED OFF

What it means

ID Card Fault.

Common causes

What to check, in order

  1. Make sure the correct ID card is firmly plugged in.
  2. Perform a power and system restart

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED steady on Internal Control Failure

Display shows: Steady ON

What it means

Internal Control Failure.

Common causes

What to check, in order

  1. Perform a power and system reset
  2. If the fault remains, replace the PIM

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED 2 flashes False Flame Error

Display shows: 2 flashes

What it means

False Flame Error.

Common causes

What to check, in order

  1. Check for proper gas valve closure
  2. Clean burner and electrodes

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the gas valve or burners is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED 3 flashes Ignition Lockout Fault

Display shows: 3 flashes

What it means

Ignition Lockout Fault.

Common causes

What to check, in order

  1. Check the gas supply

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or gas supply and pressure is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED 5 flashes Low Voltage Fault: 24 VAC input must be above 18.0 VAC

Display shows: 5 flashes

What it means

Low Voltage Fault: 24 VAC input must be above 18.0 VAC.

Common causes

What to check, in order

  1. Check the 24 VAC input voltage (must be above 18.0 VAC)

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED 7 flashes Hi-Limit Fault

Display shows: 7 flashes

What it means

Hi-Limit Fault.

Common causes

What to check, in order

  1. Check for proper water flow
  2. Check hi-limit and outlet sensor

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED 8 flashes Sensor Fault

Display shows: 8 flashes

What it means

Sensor Fault.

Common causes

What to check, in order

  1. See the VERSA for fault identification
  2. Check sensor wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED 13 flashes Hi-Temperature Delta Fault

Display shows: 13 flashes

What it means

Hi-Temperature Delta Fault.

Common causes

What to check, in order

  1. Check pump operation
  2. Confirm proper water flow across the heat exchanger

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED 14 flashes Ft-Bus Communications Fault

Display shows: 14 flashes

What it means

Ft-Bus Communications Fault.

Common causes

What to check, in order

  1. Verify the VERSA is connected and operating
  2. Check the cable between the VERSA and PIM

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

PIM red LED 15 flashes Safety circuit open

Display shows: 15 flashes

What it means

Safety circuit open.

Common causes

What to check, in order

  1. Confirm all safeties are functioning normally
  2. At the PIM, use J8 pins 5 and 6 to test continuity.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving meter tests is a job for a qualified technician.

Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.

Blue knows every code and the manual for your exact model

Ask Blue free in the Pool AI app: tell Blue the code and your model, and get the steps for your equipment.

Ask Blue free

Pool company? Give your techs Blue: every code, every manual and your customers' equipment in one app.

Give your techs Blue

Questions

What does Raypak code OUTLET SEN mean on MVB commercial heaters & boilers (504A–2004A)?

Error display item: outlet water sensor. First check: Inspect the outlet water sensor and its wiring.

What does Raypak code LIMIT SEN mean on MVB commercial heaters & boilers (504A–2004A)?

Error display item: high limit sensor. First check: Inspect the high limit sensor and its wiring.

What does Raypak code INLET SEN mean on MVB commercial heaters & boilers (504A–2004A)?

Error display item: inlet sensor. First check: Check the inlet sensor and its wiring.

What does Raypak code GAS PRESS mean on MVB commercial heaters & boilers (504A–2004A)?

Error display item: gas pressure. First check: Check PIM wiring.

What does Raypak code IGNITION mean on MVB commercial heaters & boilers (504A–2004A)?

Error display item: ignition. First check: Reset the control: push and release the RESET button.

Related

General information from the manufacturers' manuals, written in our own words. Pool AI is not affiliated with or endorsed by the brands named here; brand and model names belong to their owners. Always follow the manual for your exact model and your local codes. Work on gas, high voltage and refrigerant only by qualified, licensed people. Updated 2026-11-23.