Safety first
Gas heater: the gas valve, burners, ignition, flame sensing, venting and anything behind the cabinet panels are for a qualified gas technician. Never jumper or bypass a safety switch or limit. If you smell gas, shut off the gas supply, do not touch electrical switches, leave the area and call your gas company from outside.
Jump to a code
| Code | What it means |
|---|---|
| OUTLET SEN | Error display item: outlet water sensor |
| LIMIT SEN | Error display item: high limit sensor |
| INLET SEN | Error display item: inlet sensor |
| GAS PRESS | Error display item: gas pressure |
| IGNITION | Error display item: ignition |
| LIMIT TRIP | Boiler temperature tripped the high limit |
| FLAME | False flame detected |
| ID CARD | Identity card error |
| IGN CTRL | Internal control fault |
| DELTA T | Temperature difference between inlet and outlet exceeded the setpoint |
| LOW 24VAC | Low 24 VAC power |
| BLOW SPEED | Blower speed out of range |
| PIM red LED off | Normal operation |
| PIM red LED steady on, green power LED off | ID Card Fault |
| PIM red LED steady on | Internal Control Failure |
| PIM red LED 2 flashes | False Flame Error |
| PIM red LED 3 flashes | Ignition Lockout Fault |
| PIM red LED 5 flashes | Low Voltage Fault: 24 VAC input must be above 18.0 VAC |
| PIM red LED 7 flashes | Hi-Limit Fault |
| PIM red LED 8 flashes | Sensor Fault |
| PIM red LED 13 flashes | Hi-Temperature Delta Fault |
| PIM red LED 14 flashes | Ft-Bus Communications Fault |
| PIM red LED 15 flashes | Safety circuit open |
OUTLET SEN Error display item: outlet water sensor
What it means
Error display item: outlet water sensor.
Common causes
- Outlet water sensor or its wiring
What to check, in order
- Inspect the outlet water sensor and its wiring.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
LIMIT SEN Error display item: high limit sensor
What it means
Error display item: high limit sensor.
Common causes
- High limit sensor or its wiring
What to check, in order
- Inspect the high limit sensor and its wiring.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
INLET SEN Error display item: inlet sensor
What it means
Error display item: inlet sensor.
Common causes
- Inlet sensor or its wiring
What to check, in order
- Check the inlet sensor and its wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
GAS PRESS Error display item: gas pressure
What it means
Error display item: gas pressure.
What to check, in order
- Check PIM wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or gas supply and pressure is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
IGNITION Error display item: ignition
What it means
Error display item: ignition.
What to check, in order
- Reset the control: push and release the RESET button
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
LIMIT TRIP Boiler temperature tripped the high limit
What it means
Boiler temperature tripped the high limit.
Common causes
- Boiler temperature reached the high limit
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
FLAME False flame detected
What it means
False flame detected.
Common causes
- False flame
What to check, in order
- Shut off the gas supply
- Recycle power
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
ID CARD Identity card error
What it means
Identity card error.
What to check, in order
- Check the ID card and wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
IGN CTRL Internal control fault
What it means
Internal control fault.
Common causes
- Internal control fault
What to check, in order
- Reset power
- Replace the control
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
DELTA T Temperature difference between inlet and outlet exceeded the setpoint
What it means
Temperature difference between inlet and outlet exceeded the setpoint.
Common causes
- Inlet-outlet temperature difference too high
What to check, in order
- Check water flow
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
LOW 24VAC Low 24 VAC power
What it means
Low 24 VAC power.
Common causes
- Low 24 VAC supply
What to check, in order
- Check power supply wiring and transformer
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage, wiring or electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
BLOW SPEED Blower speed out of range
What it means
Blower speed out of range.
Common causes
- Blower speed out of range
What to check, in order
- Check blower wiring and blower
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 49. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED off Normal operation
Display shows: Off
What it means
Normal operation.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED steady on, green power LED off ID Card Fault
Display shows: Red LED steady ON, Green Power LED OFF
What it means
ID Card Fault.
Common causes
- ID card missing, wrong or not securely connected
What to check, in order
- Make sure the correct ID card is firmly plugged in.
- Perform a power and system restart
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED steady on Internal Control Failure
Display shows: Steady ON
What it means
Internal Control Failure.
Common causes
- PIM internal control fault
What to check, in order
- Perform a power and system reset
- If the fault remains, replace the PIM
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED 2 flashes False Flame Error
Display shows: 2 flashes
What it means
False Flame Error.
Common causes
- False flame signal
What to check, in order
- Check for proper gas valve closure
- Clean burner and electrodes
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the gas valve or burners is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED 3 flashes Ignition Lockout Fault
Display shows: 3 flashes
What it means
Ignition Lockout Fault.
Common causes
- Ignition lockout
What to check, in order
- Check the gas supply
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or gas supply and pressure is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED 5 flashes Low Voltage Fault: 24 VAC input must be above 18.0 VAC
Display shows: 5 flashes
What it means
Low Voltage Fault: 24 VAC input must be above 18.0 VAC.
Common causes
- 24 VAC input at or below 18.0 VAC
What to check, in order
- Check the 24 VAC input voltage (must be above 18.0 VAC)
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED 7 flashes Hi-Limit Fault
Display shows: 7 flashes
What it means
Hi-Limit Fault.
Common causes
- High limit reached
What to check, in order
- Check for proper water flow
- Check hi-limit and outlet sensor
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED 8 flashes Sensor Fault
Display shows: 8 flashes
What it means
Sensor Fault.
Common causes
- Sensor fault
What to check, in order
- See the VERSA for fault identification
- Check sensor wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED 13 flashes Hi-Temperature Delta Fault
Display shows: 13 flashes
What it means
Hi-Temperature Delta Fault.
Common causes
- Temperature rise (Delta T) too high
What to check, in order
- Check pump operation
- Confirm proper water flow across the heat exchanger
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED 14 flashes Ft-Bus Communications Fault
Display shows: 14 flashes
What it means
Ft-Bus Communications Fault.
Common causes
- Communication lost between VERSA and PIM
What to check, in order
- Verify the VERSA is connected and operating
- Check the cable between the VERSA and PIM
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
PIM red LED 15 flashes Safety circuit open
Display shows: 15 flashes
What it means
Safety circuit open.
Common causes
- Safety circuit open
What to check, in order
- Confirm all safeties are functioning normally
- At the PIM, use J8 pins 5 and 6 to test continuity.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving meter tests is a job for a qualified technician.
Applies to: 504A, 754A, 1104A, 1504A, 2004A
Source: the Raypak installation & operating manual (P/N 241512 Rev. 10), page 50. maker's manual (PDF) The same code is also in 2 other manuals or revisions.
Blue knows every code and the manual for your exact model
Ask Blue free in the Pool AI app: tell Blue the code and your model, and get the steps for your equipment.
Ask Blue freePool company? Give your techs Blue: every code, every manual and your customers' equipment in one app.
Questions
What does Raypak code OUTLET SEN mean on MVB commercial heaters & boilers (504A–2004A)?
Error display item: outlet water sensor. First check: Inspect the outlet water sensor and its wiring.
What does Raypak code LIMIT SEN mean on MVB commercial heaters & boilers (504A–2004A)?
Error display item: high limit sensor. First check: Inspect the high limit sensor and its wiring.
What does Raypak code INLET SEN mean on MVB commercial heaters & boilers (504A–2004A)?
Error display item: inlet sensor. First check: Check the inlet sensor and its wiring.
What does Raypak code GAS PRESS mean on MVB commercial heaters & boilers (504A–2004A)?
Error display item: gas pressure. First check: Check PIM wiring.
What does Raypak code IGNITION mean on MVB commercial heaters & boilers (504A–2004A)?
Error display item: ignition. First check: Reset the control: push and release the RESET button.
Related
- Raypak Digital pool heaters 206A–407A
- Raypak Low NOx pool heaters 207A–407A
- Raypak Atmospheric heaters 268A & 408A
- Raypak Avia heaters (264 & 404)
- Raypak Above-ground heaters 106 & 156
- Raypak X94 Professional SR-410 heater
- Raypak XTherm commercial heaters & boilers
- Raypak VERSA IC boiler control
- Raypak ELS electric pool & spa heaters
- All Raypak error codes
- All pool equipment error codes
General information from the manufacturers' manuals, written in our own words. Pool AI is not affiliated with or endorsed by the brands named here; brand and model names belong to their owners. Always follow the manual for your exact model and your local codes. Work on gas, high voltage and refrigerant only by qualified, licensed people. Updated 2026-11-23.