169 codes for VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire and 1 more models: what each one means, what to check first, and when to call a pro.

Safety first

Gas heater: the gas valve, burners, ignition, flame sensing, venting and anything behind the cabinet panels are for a qualified gas technician. Never jumper or bypass a safety switch or limit. If you smell gas, shut off the gas supply, do not touch electrical switches, leave the area and call your gas company from outside.

Jump to a code

CodeWhat it means
PIM red LED offNormal operation
PIM red LED steady on, green power LED offID Card Fault
PIM red LED steady onInternal Control Fault
PIM red LED 1 flashAirflow Fault
PIM red LED 2 flashesFalse Flame Error
PIM red LED 3 flashesIgnition Lockout Fault
PIM red LED 4 flashesIgnition Proving Current Fault
PIM red LED 5 flashesLow Voltage Fault: 24VAC input must be above 18.0VAC for proper operation
PIM red LED 7 flashesHi-Limit Fault
PIM red LED 8 flashesSensor Fault
PIM red LED 9 flashesNo error mode is given for this
PIM red LED 10 flashesWater Pressure Fault
PIM red LED 11 flashesBlower Speed Fault
PIM red LED 12 flashesNo error mode is given for this
PIM red LED 13 flashesHi-Temperature Delta Fault
PIM red LED 14 flashesFt_bus Communications Fault
PIM red LED 15 flashesGeneral Limit Circuit Fault
Primary PIM Fault ID 1Hi-Delta only, primary PIM fault: Airflow Fault, triggered by Open or close fault
Secondary PIM Fault ID 1Hi-Delta only, secondary PIM fault: Airflow Fault, triggered by Open or close fault
Primary PIM Fault ID 2Hi-Delta only, primary PIM fault: Flame Error, triggered by False flame signal
Secondary PIM Fault ID 2Hi-Delta only, secondary PIM fault: Flame Error, triggered by False flame signal
Primary PIM Fault ID 3Hi-Delta only, primary PIM fault: Hard Lockout, triggered by Ignition Lockout
Secondary PIM Fault ID 3Hi-Delta only, secondary PIM fault: Hard Lockout, triggered by Ignition Lockout
Primary PIM Fault ID 4Hi-Delta only, primary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in…
Secondary PIM Fault ID 4Hi-Delta only, secondary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in…
Primary PIM Fault ID 5Hi-Delta only, primary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac
Secondary PIM Fault ID 5Hi-Delta only, secondary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac
Primary PIM Fault ID 6Hi-Delta only, primary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached
Secondary PIM Fault ID 6Hi-Delta only, secondary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached
Primary PIM Fault ID 7Hi-Delta only, primary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached
Secondary PIM Fault ID 7Hi-Delta only, secondary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached
Primary PIM Fault ID 9Hi-Delta only, primary PIM fault: Safety #1 Fault, triggered by Safety input fault detected
Secondary PIM Fault ID 9Hi-Delta only, secondary PIM fault: Safety #1 Fault, triggered by Safety input fault detected
Primary PIM Fault ID 10Hi-Delta only, primary PIM fault: Water flow Fault, triggered by Open or close fault
Secondary PIM Fault ID 10Hi-Delta only, secondary PIM fault: Water flow Fault, triggered by Open or close fault
Primary PIM Fault ID 11Hi-Delta only, primary PIM fault: Blower Speed Fault, triggered by RPM out of expected range
Secondary PIM Fault ID 11Hi-Delta only, secondary PIM fault: Blower Speed Fault, triggered by RPM out of expected range
Primary PIM Fault ID 12Hi-Delta only, primary PIM fault: LWCO Fault, triggered by LWCO Open
Secondary PIM Fault ID 12Hi-Delta only, secondary PIM fault: Interlock Fault, triggered by Interlock Open
Primary PIM Fault ID 13Hi-Delta only, primary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold
Secondary PIM Fault ID 13Hi-Delta only, secondary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold
Primary PIM Fault ID 14Hi-Delta only, primary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications
Secondary PIM Fault ID 14Hi-Delta only, secondary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications
Primary PIM Fault ID 15Hi-Delta only, primary PIM fault: ID Card Fault, triggered by Invalid or Missing card
Secondary PIM Fault ID 15Hi-Delta only, secondary PIM fault: ID Card Fault, triggered by Invalid or Missing card
Primary PIM Fault ID 16Hi-Delta only, primary PIM fault: Outlet Sensor Fault, triggered by Open/short
Secondary PIM Fault ID 16Hi-Delta only, secondary PIM fault: Outlet Sensor Fault, triggered by Open/short
Primary PIM Fault ID 17Hi-Delta only, primary PIM fault: Inlet Sensor Fault, triggered by Open/short
Secondary PIM Fault ID 17Hi-Delta only, secondary PIM fault: Inlet Sensor Fault, triggered by Open/short
Primary PIM Fault ID 18Hi-Delta only, primary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet
Secondary PIM Fault ID 18Hi-Delta only, secondary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet
Primary PIM Fault ID 19Hi-Delta only, primary PIM fault: Vent Sensor Fault, triggered by Open/short
Secondary PIM Fault ID 19Hi-Delta only, secondary PIM fault: Vent Sensor Fault, triggered by Open/short
Primary PIM Fault ID 20Hi-Delta only, primary PIM fault: Safety #2 Fault, triggered by Safety input fault detected
Secondary PIM Fault ID 20Hi-Delta only, secondary PIM fault: Safety #2 Fault, triggered by Safety input fault detected
OUTLET SENHeater outlet sensor fault (3-sec delay)
LIMIT SENHigh limit sensor fault (3-sec delay)
INLET SENHeater inlet sensor fault (3-sec delay)
INTERLOCKInterlock is open
WATER PRESSWater pressure switch fault (if equipped)
AIR PRESSAir pressure switch fault (if equipped)
GAS PRESSGas pressure switch fault (if equipped) with a 90-sec delay
IGNITIONIgnition fault
LIMIT TRIPBoiler outlet temperature tripped the high limit
FLAMEFlame is sensed with no call-for-heat (3-sec delay)
IGN CTRLInternal PIM control fault (3-sec delay)
Delta-TDelta-T temperature went past its threshold (3-sec delay)
LO HSI CURHSI current is low at the PIM control (3-sec delay)
LOW 24VAC24VAC power is low at the PIM control (3-sec delay)
BLOW SPEEDBlower speed (rpm) is outside its range (3-sec delay)
SAFETY INPUTAdditional factory-installed safety fault (3-sec delay)
CTRL SETUPEEPROM setup block could not be read at power-up
SUPPLY ERRSystem sensor shorted or open
DHWSUP ERRPlant sensor shorted or open
OUTDOOR ERROutdoor air sensor shorted or open
DHW ERRIndirect DHW sensor shorted or open
TANK ERRTank sensor shorted or open
POOL ERRPool sensor shorted or open
DEV LOSTDevice xx on the heater bus is lost
DEV ERRMore than 1 master detected on the tN4 bus (3-sec)
PIM 1 ERRCommunication with PIM 1 was working, then dropped (3-sec)
PIM 2 ERRCommunication with PIM 2 was working, then dropped (3-sec)
PIM 3 ERRCommunication with PIM 3 was working, then dropped (3-sec)
PIM 4 ERRCommunication with PIM 4 was working, then dropped (3-sec)
CONDENSATECondensate switch has tripped (3-sec)
VENT TEMPVent temperature switch has tripped (1-sec)
AUTO LIMITAutomatic high limit has tripped (3-sec)
LOW WATERLow water cut-off has tripped (1-sec)
VENT BLOCKBlocked vent switch has tripped (3-sec)
LOW GASLow gas pressure switch has tripped (1-sec)
HIGH GASHigh gas pressure switch has tripped (1-sec)
EXTRAExtra limit switch has tripped (1-sec)
WATER FLOWWater flow switch tripped
BLOWERBlower air pressure switch has tripped (10-sec)
OPTION 1Factory option #1 switch tripped
OPTION 2Factory option #2 switch tripped
OPTION 3Factory option #3 switch tripped
E0Modbus/VERSA error code: No Error
E1Modbus/VERSA error code: EEPROM Fault
E2Modbus/VERSA error code: Outdoor Sensor (S4)
E3Modbus/VERSA error code: System Sensor (S3)
E4Modbus/VERSA error code: Plant Sensor IND Supply (S6)
E5Modbus/VERSA error code: Mix Sensor
E6Modbus/VERSA error code: DHW Sensor (S5)
E7Modbus/VERSA error code: Tank Sensor
E8Modbus/VERSA error code: Pool Sensor
E9Modbus/VERSA error code: No master
E10Modbus/VERSA error code: No PIM1
E11Modbus/VERSA error shown as "Dev Lost / No VRS 2 or No PIM 2"
E12Modbus/VERSA error shown as "Dev Lost / No VRS 3 or No PIM 3"
E13Modbus/VERSA error shown as "Dev Lost / No VRS 4 or No PIM 4"
E14Modbus/VERSA error code: Condensate Switch
E15Modbus/VERSA error code: Vent Temperature
E16Modbus/VERSA error code: Auto Hi-Limit
E17Modbus/VERSA error code: Low Water Cutoff Module
E18Modbus/VERSA error code: Blocked Vent Switch
E19Modbus/VERSA error code: Low Gas Pressure
E20Modbus/VERSA error code: High Gas Pressure
E21Modbus/VERSA error code: Extra Safety Input
E22Modbus/VERSA error code: Flow Switch
E23Modbus/VERSA error code: Air Pressure Switch
E24Modbus/VERSA error code: Safety Option 1
E25Modbus/VERSA error code: Safety Option 2
E26Modbus/VERSA error code: Safety Option 3
E27Modbus/VERSA error code: LWCO (Jumper)
E28Modbus/VERSA error code: Water Pressure (Jumper)
E29Modbus/VERSA error code: Air Pressure (Jumper)
E30Modbus/VERSA error code: Gas Pressure (Jumper)
E31Modbus/VERSA error code: Boiler Outlet Sensor
E32Modbus/VERSA error code: Boiler Inlet Sensor
E33Modbus/VERSA error code: Vent Sensor
E34Modbus/VERSA error code: High Limit Sensor (Manual-reset)
E35Modbus/VERSA error code: Ignition Failure
E36Modbus/VERSA error code: Vent Hi-Limit
E37Modbus/VERSA error code: Boiler Hi-Limit
E38Modbus/VERSA error code: False Flame
E39Modbus/VERSA error code: OEM ID Card
E40Modbus/VERSA error code: Internal Fault
E41Modbus/VERSA error code: Delta-T Max
E42Modbus/VERSA error code: HSI Proof
E43Modbus/VERSA error code: Low Voltage
E44Modbus/VERSA error code: Blower Speed
E45Modbus/VERSA error code: Safety Input
E46Modbus/VERSA error code: Duplicate Master
E47Modbus/VERSA error code: Device Error
E48Modbus/VERSA error code: Device Lost
E49Modbus/VERSA error code: Supply Sensor / Pool Max Error
E50Modbus/VERSA error code: MIX Lock Error
E51Modbus/VERSA error code: PIM 2 Ignition Failure
E52Modbus/VERSA error code: PIM 2 False Flame
E53Modbus/VERSA error code: PIM 2 OEM ID Error
E54Modbus/VERSA error code: PIM 2 Internal Failure
E55Modbus/VERSA error code: PIM 2 HSI Proof
E56Modbus/VERSA error code: PIM 2 Low Voltage
E57Modbus/VERSA error code: PIM 2 Blower Speed Flow Read Error
E58Modbus/VERSA error code: PIM 2 Safety Input
E59Modbus/VERSA error code: Flow Read Error
E60Modbus/VERSA error code: Under-Flow Error
E61Modbus/VERSA error code: Flow Warning
E62Modbus/VERSA error code: Device Lost, Cascade Follower # 5
E63Modbus/VERSA error code: Device Lost, Cascade Follower # 6
E64Modbus/VERSA error code: Device Lost, Cascade Follower # 7
E65Modbus/VERSA error code: Device Lost, Cascade Follower # 8
E66Modbus/VERSA error code: Auto Hi-Limit from PIM
E67Modbus/VERSA error code: Manual Hi-Limit from PIM
E68Modbus/VERSA error code: Blower Loss from Tach Signal
E69Modbus/VERSA error code: Flame Loss Warning
PIM red LED 6 flashesVent Temperature Fault
ID CARDInvalid/missing ID card (3-sec delay)

PIM red LED off Normal operation

Display shows: Red LED OFF

What it means

Normal operation.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED steady on, green power LED off ID Card Fault

Display shows: Red LED Steady ON, Green Power LED OFF

What it means

ID Card Fault.

Common causes

What to check, in order

  1. Make sure the correct ID card is firmly plugged in.
  2. Perform a power and system reset

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED steady on Internal Control Fault

Display shows: Red LED Steady ON

What it means

Internal Control Fault.

Common causes

What to check, in order

  1. Perform a power and system reset
  2. If the fault remains, replace the PIM

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 1 flash Airflow Fault

Display shows: Red LED – 1 Flash

What it means

Airflow Fault.

Common causes

What to check, in order

  1. Check blower operation and air flow switch

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 2 flashes False Flame Error

Display shows: Red LED – 2 Flashes

What it means

False Flame Error.

Common causes

What to check, in order

  1. Check for proper gas valve closure
  2. Clean burner and electrodes

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the gas valve or burners is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 3 flashes Ignition Lockout Fault

Display shows: Red LED – 3 Flashes

What it means

Ignition Lockout Fault.

Common causes

What to check, in order

  1. Check the gas supply
  2. Check transformer
  3. Check igniters
  4. Check wiring
  5. Press the reset button on the PIM/membrane switch
  6. Recycle power

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control, wiring, electrical parts (fuses, relays, transformers) or gas supply and pressure is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 4 flashes Ignition Proving Current Fault

Display shows: Red LED – 4 Flashes

What it means

Ignition Proving Current Fault.

Common causes

What to check, in order

  1. Check the HSI element (models with a hot surface igniter)
  2. Replace as necessary

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 5 flashes Low Voltage Fault: 24VAC input must be above 18.0VAC for proper operation

Display shows: Red LED – 5 Flashes

What it means

Low Voltage Fault: 24VAC input must be above 18.0VAC for proper operation.

Common causes

What to check, in order

  1. Check the 24VAC input voltage (must be above 18.0VAC)
  2. Replace transformer as necessary

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage or electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

Ask Blue freeGive your techs Blue

PIM red LED 7 flashes Hi-Limit Fault

Display shows: Red LED – 7 Flashes

What it means

Hi-Limit Fault.

Common causes

What to check, in order

  1. Check for proper water flow
  2. Check hi-limit setting and outlet sensor

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 8 flashes Sensor Fault

Display shows: Red LED – 8 Flashes

What it means

Sensor Fault.

Common causes

What to check, in order

  1. Check the VERSA IC for fault identification
  2. Check sensor and wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 9 flashes No error mode is given for this

Display shows: Red LED – 9 Flashes

What it means

No error mode is given for this; check the wiring.

What to check, in order

  1. At J8, pins 1 and 3, the wiring should be checked for a missing or loose jumper.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 10 flashes Water Pressure Fault

Display shows: Red LED – 10 Flashes

What it means

Water Pressure Fault.

Common causes

What to check, in order

  1. Check system piping for leaks
  2. Check the water pressure switch (if equipped) and connections
  3. On the PIM, J1 pins 6 and 7: check the wiring for a missing or loose jumper.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 11 flashes Blower Speed Fault

Display shows: Red LED – 11 Flashes

What it means

Blower Speed Fault.

Common causes

What to check, in order

  1. Confirm the tachometer signal and connections at terminals J10 on the PIM.
  2. Confirm power to the boiler is at or above the minimum required

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 12 flashes No error mode is given for this

Display shows: Red LED – 12 Flashes

What it means

No error mode is given for this; check the wiring.

What to check, in order

  1. On the PIM, J1 pins 3 and 4: check the wiring for a missing or loose jumper.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 13 flashes Hi-Temperature Delta Fault

Display shows: Red LED – 13 Flashes

What it means

Hi-Temperature Delta Fault.

Common causes

What to check, in order

  1. Check pump operation
  2. Confirm proper water flow across the heat exchanger (Delta-T)

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 14 flashes Ft_bus Communications Fault

Display shows: Red LED – 14 Flashes

What it means

Ft_bus Communications Fault.

Common causes

What to check, in order

  1. Confirm the VERSA IC is connected and working correctly.
  2. Inspect the cable that runs between the PIM and the VERSA IC.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

PIM red LED 15 flashes General Limit Circuit Fault

Display shows: Red LED – 15 Flashes

What it means

General Limit Circuit Fault.

Common causes

What to check, in order

  1. Look at the VERSA IC for fault indications and troubleshooting details.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

Primary PIM Fault ID 1 Hi-Delta only, primary PIM fault: Airflow Fault, triggered by Open or close fault

Display shows: Fault ID 1

What it means

Hi-Delta only, primary PIM fault: Airflow Fault, triggered by Open or close fault. LED blinks 1 time. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 1 Hi-Delta only, secondary PIM fault: Airflow Fault, triggered by Open or close fault

Display shows: Fault ID 1

What it means

Hi-Delta only, secondary PIM fault: Airflow Fault, triggered by Open or close fault. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 2 Hi-Delta only, primary PIM fault: Flame Error, triggered by False flame signal

Display shows: Fault ID 2

What it means

Hi-Delta only, primary PIM fault: Flame Error, triggered by False flame signal. LED blinks 2 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 2 Hi-Delta only, secondary PIM fault: Flame Error, triggered by False flame signal

Display shows: Fault ID 2

What it means

Hi-Delta only, secondary PIM fault: Flame Error, triggered by False flame signal. LED blinks 2 times. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 3 Hi-Delta only, primary PIM fault: Hard Lockout, triggered by Ignition Lockout

Display shows: Fault ID 3

What it means

Hi-Delta only, primary PIM fault: Hard Lockout, triggered by Ignition Lockout. LED blinks 3 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 3 Hi-Delta only, secondary PIM fault: Hard Lockout, triggered by Ignition Lockout

Display shows: Fault ID 3

What it means

Hi-Delta only, secondary PIM fault: Hard Lockout, triggered by Ignition Lockout. LED blinks 3 times. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 4 Hi-Delta only, primary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in…

Display shows: Fault ID 4

What it means

Hi-Delta only, primary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in range. LED blinks 4 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 4 Hi-Delta only, secondary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in…

Display shows: Fault ID 4

What it means

Hi-Delta only, secondary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in range. LED blinks 4 times. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 5 Hi-Delta only, primary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac

Display shows: Fault ID 5

What it means

Hi-Delta only, primary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac. LED blinks 5 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage or electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 5 Hi-Delta only, secondary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac

Display shows: Fault ID 5

What it means

Hi-Delta only, secondary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac. LED blinks 5 times. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage or electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 6 Hi-Delta only, primary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached

Display shows: Fault ID 6

What it means

Hi-Delta only, primary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached. LED blinks 6 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) or venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 6 Hi-Delta only, secondary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached

Display shows: Fault ID 6

What it means

Hi-Delta only, secondary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) or venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 7 Hi-Delta only, primary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached

Display shows: Fault ID 7

What it means

Hi-Delta only, primary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached. LED blinks 7 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 7 Hi-Delta only, secondary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached

Display shows: Fault ID 7

What it means

Hi-Delta only, secondary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 9 Hi-Delta only, primary PIM fault: Safety #1 Fault, triggered by Safety input fault detected

Display shows: Fault ID 9

What it means

Hi-Delta only, primary PIM fault: Safety #1 Fault, triggered by Safety input fault detected. LED blinks 9 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 9 Hi-Delta only, secondary PIM fault: Safety #1 Fault, triggered by Safety input fault detected

Display shows: Fault ID 9

What it means

Hi-Delta only, secondary PIM fault: Safety #1 Fault, triggered by Safety input fault detected. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 10 Hi-Delta only, primary PIM fault: Water flow Fault, triggered by Open or close fault

Display shows: Fault ID 10

What it means

Hi-Delta only, primary PIM fault: Water flow Fault, triggered by Open or close fault. LED blinks 10 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 10 Hi-Delta only, secondary PIM fault: Water flow Fault, triggered by Open or close fault

Display shows: Fault ID 10

What it means

Hi-Delta only, secondary PIM fault: Water flow Fault, triggered by Open or close fault. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 11 Hi-Delta only, primary PIM fault: Blower Speed Fault, triggered by RPM out of expected range

Display shows: Fault ID 11

What it means

Hi-Delta only, primary PIM fault: Blower Speed Fault, triggered by RPM out of expected range. LED blinks 11 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 11 Hi-Delta only, secondary PIM fault: Blower Speed Fault, triggered by RPM out of expected range

Display shows: Fault ID 11

What it means

Hi-Delta only, secondary PIM fault: Blower Speed Fault, triggered by RPM out of expected range. LED blinks 11 times. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 12 Hi-Delta only, primary PIM fault: LWCO Fault, triggered by LWCO Open

Display shows: Fault ID 12

What it means

Hi-Delta only, primary PIM fault: LWCO Fault, triggered by LWCO Open. LED blinks 12 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 12 Hi-Delta only, secondary PIM fault: Interlock Fault, triggered by Interlock Open

Display shows: Fault ID 12

What it means

Hi-Delta only, secondary PIM fault: Interlock Fault, triggered by Interlock Open. LED blinks 12 times. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 13 Hi-Delta only, primary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold

Display shows: Fault ID 13

What it means

Hi-Delta only, primary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold. LED blinks 13 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 13 Hi-Delta only, secondary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold

Display shows: Fault ID 13

What it means

Hi-Delta only, secondary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 14 Hi-Delta only, primary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications

Display shows: Fault ID 14

What it means

Hi-Delta only, primary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications. LED blinks 14 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 14 Hi-Delta only, secondary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications

Display shows: Fault ID 14

What it means

Hi-Delta only, secondary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications. LED blinks 14 times. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 15 Hi-Delta only, primary PIM fault: ID Card Fault, triggered by Invalid or Missing card

Display shows: Fault ID 15

What it means

Hi-Delta only, primary PIM fault: ID Card Fault, triggered by Invalid or Missing card. LED shows red on, green off. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 15 Hi-Delta only, secondary PIM fault: ID Card Fault, triggered by Invalid or Missing card

Display shows: Fault ID 15

What it means

Hi-Delta only, secondary PIM fault: ID Card Fault, triggered by Invalid or Missing card. LED shows red on, green off. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 16 Hi-Delta only, primary PIM fault: Outlet Sensor Fault, triggered by Open/short

Display shows: Fault ID 16

What it means

Hi-Delta only, primary PIM fault: Outlet Sensor Fault, triggered by Open/short. LED blinks 8 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 16 Hi-Delta only, secondary PIM fault: Outlet Sensor Fault, triggered by Open/short

Display shows: Fault ID 16

What it means

Hi-Delta only, secondary PIM fault: Outlet Sensor Fault, triggered by Open/short. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 17 Hi-Delta only, primary PIM fault: Inlet Sensor Fault, triggered by Open/short

Display shows: Fault ID 17

What it means

Hi-Delta only, primary PIM fault: Inlet Sensor Fault, triggered by Open/short. LED blinks 8 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 17 Hi-Delta only, secondary PIM fault: Inlet Sensor Fault, triggered by Open/short

Display shows: Fault ID 17

What it means

Hi-Delta only, secondary PIM fault: Inlet Sensor Fault, triggered by Open/short. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 18 Hi-Delta only, primary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet

Display shows: Fault ID 18

What it means

Hi-Delta only, primary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet. LED blinks 8 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 18 Hi-Delta only, secondary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet

Display shows: Fault ID 18

What it means

Hi-Delta only, secondary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 19 Hi-Delta only, primary PIM fault: Vent Sensor Fault, triggered by Open/short

Display shows: Fault ID 19

What it means

Hi-Delta only, primary PIM fault: Vent Sensor Fault, triggered by Open/short. LED blinks 8 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) or venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 19 Hi-Delta only, secondary PIM fault: Vent Sensor Fault, triggered by Open/short

Display shows: Fault ID 19

What it means

Hi-Delta only, secondary PIM fault: Vent Sensor Fault, triggered by Open/short. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) or venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Primary PIM Fault ID 20 Hi-Delta only, primary PIM fault: Safety #2 Fault, triggered by Safety input fault detected

Display shows: Fault ID 20

What it means

Hi-Delta only, primary PIM fault: Safety #2 Fault, triggered by Safety input fault detected. LED blinks 15 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

Secondary PIM Fault ID 20 Hi-Delta only, secondary PIM fault: Safety #2 Fault, triggered by Safety input fault detected

Display shows: Fault ID 20

What it means

Hi-Delta only, secondary PIM fault: Safety #2 Fault, triggered by Safety input fault detected. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.

Common causes

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)

OUTLET SEN Heater outlet sensor fault (3-sec delay)

What it means

Heater outlet sensor fault (3-sec delay).

Common causes

What to check, in order

  1. Check outlet sensor
  2. Check outlet sensor wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

LIMIT SEN High limit sensor fault (3-sec delay)

What it means

High limit sensor fault (3-sec delay).

Common causes

What to check, in order

  1. Check limit sensor
  2. Check limit sensor wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

INLET SEN Heater inlet sensor fault (3-sec delay)

What it means

Heater inlet sensor fault (3-sec delay).

Common causes

What to check, in order

  1. Check inlet sensor
  2. Check inlet sensor wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

INTERLOCK Interlock is open

What it means

Interlock is open; a jumper installed at the factory is in place on shipment (90-sec delay).

Common causes

What to check, in order

  1. Check louver end switch and wiring
  2. Check combustion air damper end switch and wiring
  3. Check extractor and wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

WATER PRESS Water pressure switch fault (if equipped)

What it means

Water pressure switch fault (if equipped); factory jumper in place if not shipped with a water pressure switch (90-sec delay).

Common causes

What to check, in order

  1. Verify wiring at J1 terminals 6 & 7
  2. Check heater pump
  3. Check isolation valves

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

AIR PRESS Air pressure switch fault (if equipped)

What it means

Air pressure switch fault (if equipped); factory jumper in place if not shipped with an air pressure switch (90-sec delay).

Common causes

What to check, in order

  1. Verify wiring at J8 terminals 2 & 4
  2. Check blower(s)
  3. Check air pressure switch tubing

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

GAS PRESS Gas pressure switch fault (if equipped) with a 90-sec delay

What it means

Gas pressure switch fault (if equipped) with a 90-sec delay. A factory jumper is in place when the unit ships without a high and/or low gas pressure switch.

Common causes

What to check, in order

  1. Verify wiring at J8 terminals 1 & 3
  2. Check gas pressure switches
  3. Check gas pressure
  4. Check gas pressure switch tubing

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or gas supply and pressure is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

IGNITION Ignition fault

What it means

Ignition fault.

Common causes

What to check, in order

  1. Reset the ignition control: push either RESET button on the membrane switch or the reset button on the PIM, or recycle power

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

LIMIT TRIP Boiler outlet temperature tripped the high limit

What it means

Boiler outlet temperature tripped the high limit.

Common causes

What to check, in order

  1. If the manual-reset high limit tripped, press the reset button on the high limit control.
  2. Wait for water temperature to drop; the auto-reset high limit will reset
  3. Check pump operation
  4. Look for too much water flow through the bypass (if fitted).

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

FLAME Flame is sensed with no call-for-heat (3-sec delay)

What it means

Flame is sensed with no call-for-heat (3-sec delay).

Common causes

What to check, in order

  1. Shut off the gas supply
  2. Recycle power
  3. Check gas valve leakage

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the gas valve or gas supply and pressure is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

IGN CTRL Internal PIM control fault (3-sec delay)

What it means

Internal PIM control fault (3-sec delay).

Common causes

What to check, in order

  1. Recycle power
  2. If the error continues, replace the PIM

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

Delta-T Delta-T temperature went past its threshold (3-sec delay)

What it means

Delta-T temperature went past its threshold (3-sec delay).

Common causes

What to check, in order

  1. Check pump operation
  2. Check Delta-T setting
  3. Look for too much water flow through the bypass (if fitted).

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

LO HSI CUR HSI current is low at the PIM control (3-sec delay)

What it means

HSI current is low at the PIM control (3-sec delay).

Common causes

What to check, in order

  1. Check HSI current
  2. Replace HSI
  3. Replace PIM control

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

LOW 24VAC 24VAC power is low at the PIM control (3-sec delay)

What it means

24VAC power is low at the PIM control (3-sec delay).

Common causes

What to check, in order

  1. Check power supply
  2. Check transformer

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage or electrical parts (fuses, relays, transformers) is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

BLOW SPEED Blower speed (rpm) is outside its range (3-sec delay)

What it means

Blower speed (rpm) is outside its range (3-sec delay).

Common causes

What to check, in order

  1. Check power supply
  2. Check blower wiring to PIM
  3. Check blower type

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

SAFETY INPUT Additional factory-installed safety fault (3-sec delay)

What it means

Additional factory-installed safety fault (3-sec delay); see the product installation and operation manual.

Common causes

What to check, in order

  1. Verify wiring at J8 terminals 5 & 6

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

CTRL SETUP EEPROM setup block could not be read at power-up

What it means

EEPROM setup block could not be read at power-up; factory defaults were reloaded and operation halts until every adjustment is verified (3-sec timeout).

Common causes

What to check, in order

  1. Go through all SETUP items; resetting the VERSA to factory defaults may clear these faults.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

SUPPLY ERR System sensor shorted or open

What it means

System sensor shorted or open; the control will cease operation (3-sec).

Common causes

What to check, in order

  1. Check System sensor (S3)
  2. Check System sensor (S3) wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

DHWSUP ERR Plant sensor shorted or open

What it means

Plant sensor shorted or open; the control will cease operation (3-sec).

Common causes

What to check, in order

  1. Check Aux1 sensor
  2. Check Aux 1 sensor wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

OUTDOOR ERR Outdoor air sensor shorted or open

What it means

Outdoor air sensor shorted or open; control keeps operating assuming 32°F (0°C) outdoor (3-sec). 15 min soft lockout.

Common causes

What to check, in order

  1. Check outdoor air sensor
  2. Check outdoor air sensor wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

DHW ERR Indirect DHW sensor shorted or open

What it means

Indirect DHW sensor shorted or open; indirect DHW stops but system heating continues (3-sec).

Common causes

What to check, in order

  1. Check DHW sensor
  2. Check DHW sensor wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

TANK ERR Tank sensor shorted or open

What it means

Tank sensor shorted or open; the control will cease operation (3-sec).

Common causes

What to check, in order

  1. Check tank sensor
  2. Check tank sensor wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

POOL ERR Pool sensor shorted or open

What it means

Pool sensor shorted or open; the control will cease operation (3-sec).

Common causes

What to check, in order

  1. Check pool sensor
  2. Check pool sensor wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

DEV LOST Device xx on the heater bus is lost

What it means

Device xx on the heater bus is lost; if on the tN4 bus the zone is shown too (3-sec).

Common causes

What to check, in order

  1. Check wiring between the VERSA IC board and all PIMs on the network
  2. Check communication wiring for the BMS system

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

DEV ERR More than 1 master detected on the tN4 bus (3-sec)

What it means

More than 1 master detected on the tN4 bus (3-sec).

Common causes

What to check, in order

  1. Check DIP switches on cascaded heaters so only 1 unit is Master and the others Followers/Slave
  2. Check communication wiring at the heater with the noted address

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

PIM 1 ERR Communication with PIM 1 was working, then dropped (3-sec)

What it means

Communication with PIM 1 was working, then dropped (3-sec).

Common causes

What to check, in order

  1. Inspect the cabling and the DIP switch settings for the Master/Follower setup.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

PIM 2 ERR Communication with PIM 2 was working, then dropped (3-sec)

What it means

Communication with PIM 2 was working, then dropped (3-sec).

Common causes

What to check, in order

  1. Confirm cabling and DIP switch settings

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

PIM 3 ERR Communication with PIM 3 was working, then dropped (3-sec)

What it means

Communication with PIM 3 was working, then dropped (3-sec).

Common causes

What to check, in order

  1. Confirm cabling and DIP switch settings

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

PIM 4 ERR Communication with PIM 4 was working, then dropped (3-sec)

What it means

Communication with PIM 4 was working, then dropped (3-sec).

Common causes

What to check, in order

  1. Confirm cabling and DIP switch settings

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

CONDENSATE Condensate switch has tripped (3-sec)

What it means

Condensate switch has tripped (3-sec). 15 min soft lockout.

Common causes

What to check, in order

  1. Check for blockage of condensate drain
  2. Check condensate switch
  3. Check condensate switch wiring
  4. Check for a heat exchanger leak that may overwhelm the condensate drain

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

VENT TEMP Vent temperature switch has tripped (1-sec)

What it means

Vent temperature switch has tripped (1-sec).

Common causes

What to check, in order

  1. Check vent temperature switch
  2. Check vent temperature switch wiring
  3. Check PVC/CPVC/Polypropylene vent for damage from excessive temperatures
  4. Check vent for leaks near the vent temperature switch

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

AUTO LIMIT Automatic high limit has tripped (3-sec)

What it means

Automatic high limit has tripped (3-sec). 15 min soft lockout.

Common causes

What to check, in order

  1. Check the automatic high limit switch
  2. Check the automatic high limit switch wiring
  3. Check for proper pump operation
  4. Look for too much water flow through the bypass (if fitted).

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

LOW WATER Low water cut-off has tripped (1-sec)

What it means

Low water cut-off has tripped (1-sec).

Common causes

What to check, in order

  1. Push the reset button on the LWCO control
  2. Check LWCO probe and wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

VENT BLOCK Blocked vent switch has tripped (3-sec)

What it means

Blocked vent switch has tripped (3-sec). 15 min soft lockout.

Common causes

What to check, in order

  1. Check venting
  2. Check vent pressure switch and wiring
  3. Check vent pressure switch tubing

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

LOW GAS Low gas pressure switch has tripped (1-sec)

What it means

Low gas pressure switch has tripped (1-sec).

Common causes

What to check, in order

  1. Push the reset button on the low gas pressure switch
  2. Verify proper gas pressure
  3. Open manual gas valves fully
  4. Clean out drip leg

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the gas valve or gas supply and pressure is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

HIGH GAS High gas pressure switch has tripped (1-sec)

What it means

High gas pressure switch has tripped (1-sec).

Common causes

What to check, in order

  1. Push the reset button on the high gas pressure switch
  2. Verify proper gas pressures

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

EXTRA Extra limit switch has tripped (1-sec)

What it means

Extra limit switch has tripped (1-sec); see the product installation and operation manual for this limit.

Common causes

What to check, in order

  1. Refer to the troubleshooting section of the installation and operation instructions for this specific product.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

WATER FLOW Water flow switch tripped

What it means

Water flow switch tripped. It takes 10-sec to close, then 1-sec to reach 'FAULT' (3-sec). Soft lockout lasts 15 min.

Common causes

What to check, in order

  1. Check heater pump operation
  2. Purge air from system
  3. Replace flow switch as necessary

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

BLOWER Blower air pressure switch has tripped (10-sec)

What it means

Blower air pressure switch has tripped (10-sec). 15 min soft lockout.

Common causes

What to check, in order

  1. Check air filter
  2. Check blower
  3. Check air pressure switch hose
  4. Check wiring

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

OPTION 1 Factory option #1 switch tripped

What it means

Factory option #1 switch tripped; the fault is reported only after a 10-sec delay on the first CFH.

Common causes

What to check, in order

  1. See the wiring diagram to find out what is connected here.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

OPTION 2 Factory option #2 switch tripped

What it means

Factory option #2 switch tripped; the fault is reported only after a 30-sec delay on the first CFH.

Common causes

What to check, in order

  1. See the wiring diagram to find out what is connected here.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

OPTION 3 Factory option #3 switch tripped

What it means

Factory option #3 switch tripped; the fault is reported only after a 90-sec delay on the first CFH.

Common causes

What to check, in order

  1. See the wiring diagram to find out what is connected here.
  2. Inspect field interlocks, for example the combustion air damper proving switch.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)

E0 Modbus/VERSA error code: No Error

What it means

Modbus/VERSA error code: No Error.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E1 Modbus/VERSA error code: EEPROM Fault

What it means

Modbus/VERSA error code: EEPROM Fault.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E2 Modbus/VERSA error code: Outdoor Sensor (S4)

What it means

Modbus/VERSA error code: Outdoor Sensor (S4).

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E3 Modbus/VERSA error code: System Sensor (S3)

What it means

Modbus/VERSA error code: System Sensor (S3).

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E4 Modbus/VERSA error code: Plant Sensor IND Supply (S6)

What it means

Modbus/VERSA error code: Plant Sensor IND Supply (S6).

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E5 Modbus/VERSA error code: Mix Sensor

What it means

Modbus/VERSA error code: Mix Sensor.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E6 Modbus/VERSA error code: DHW Sensor (S5)

What it means

Modbus/VERSA error code: DHW Sensor (S5).

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E7 Modbus/VERSA error code: Tank Sensor

What it means

Modbus/VERSA error code: Tank Sensor.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E8 Modbus/VERSA error code: Pool Sensor

What it means

Modbus/VERSA error code: Pool Sensor.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E9 Modbus/VERSA error code: No master

What it means

Modbus/VERSA error code: No master.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E10 Modbus/VERSA error code: No PIM1

What it means

Modbus/VERSA error code: No PIM1.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E11 Modbus/VERSA error shown as "Dev Lost / No VRS 2 or No PIM 2"

What it means

Modbus/VERSA error shown as "Dev Lost / No VRS 2 or No PIM 2".

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E12 Modbus/VERSA error shown as "Dev Lost / No VRS 3 or No PIM 3"

What it means

Modbus/VERSA error shown as "Dev Lost / No VRS 3 or No PIM 3".

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E13 Modbus/VERSA error shown as "Dev Lost / No VRS 4 or No PIM 4"

What it means

Modbus/VERSA error shown as "Dev Lost / No VRS 4 or No PIM 4".

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E14 Modbus/VERSA error code: Condensate Switch

What it means

Modbus/VERSA error code: Condensate Switch.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E15 Modbus/VERSA error code: Vent Temperature

What it means

Modbus/VERSA error code: Vent Temperature.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E16 Modbus/VERSA error code: Auto Hi-Limit

What it means

Modbus/VERSA error code: Auto Hi-Limit.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E17 Modbus/VERSA error code: Low Water Cutoff Module

What it means

Modbus/VERSA error code: Low Water Cutoff Module.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E18 Modbus/VERSA error code: Blocked Vent Switch

What it means

Modbus/VERSA error code: Blocked Vent Switch.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E19 Modbus/VERSA error code: Low Gas Pressure

What it means

Modbus/VERSA error code: Low Gas Pressure.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E20 Modbus/VERSA error code: High Gas Pressure

What it means

Modbus/VERSA error code: High Gas Pressure.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E21 Modbus/VERSA error code: Extra Safety Input

What it means

Modbus/VERSA error code: Extra Safety Input.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E22 Modbus/VERSA error code: Flow Switch

What it means

Modbus/VERSA error code: Flow Switch.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E23 Modbus/VERSA error code: Air Pressure Switch

What it means

Modbus/VERSA error code: Air Pressure Switch.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E24 Modbus/VERSA error code: Safety Option 1

What it means

Modbus/VERSA error code: Safety Option 1.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E25 Modbus/VERSA error code: Safety Option 2

What it means

Modbus/VERSA error code: Safety Option 2.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E26 Modbus/VERSA error code: Safety Option 3

What it means

Modbus/VERSA error code: Safety Option 3.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E27 Modbus/VERSA error code: LWCO (Jumper)

What it means

Modbus/VERSA error code: LWCO (Jumper).

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E28 Modbus/VERSA error code: Water Pressure (Jumper)

What it means

Modbus/VERSA error code: Water Pressure (Jumper).

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E29 Modbus/VERSA error code: Air Pressure (Jumper)

What it means

Modbus/VERSA error code: Air Pressure (Jumper).

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E30 Modbus/VERSA error code: Gas Pressure (Jumper)

What it means

Modbus/VERSA error code: Gas Pressure (Jumper).

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E31 Modbus/VERSA error code: Boiler Outlet Sensor

What it means

Modbus/VERSA error code: Boiler Outlet Sensor.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E32 Modbus/VERSA error code: Boiler Inlet Sensor

What it means

Modbus/VERSA error code: Boiler Inlet Sensor.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E33 Modbus/VERSA error code: Vent Sensor

What it means

Modbus/VERSA error code: Vent Sensor.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E34 Modbus/VERSA error code: High Limit Sensor (Manual-reset)

What it means

Modbus/VERSA error code: High Limit Sensor (Manual-reset).

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E35 Modbus/VERSA error code: Ignition Failure

What it means

Modbus/VERSA error code: Ignition Failure.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E36 Modbus/VERSA error code: Vent Hi-Limit

What it means

Modbus/VERSA error code: Vent Hi-Limit.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E37 Modbus/VERSA error code: Boiler Hi-Limit

What it means

Modbus/VERSA error code: Boiler Hi-Limit.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E38 Modbus/VERSA error code: False Flame

What it means

Modbus/VERSA error code: False Flame.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E39 Modbus/VERSA error code: OEM ID Card

What it means

Modbus/VERSA error code: OEM ID Card.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E40 Modbus/VERSA error code: Internal Fault

What it means

Modbus/VERSA error code: Internal Fault.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E41 Modbus/VERSA error code: Delta-T Max

What it means

Modbus/VERSA error code: Delta-T Max.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E42 Modbus/VERSA error code: HSI Proof

What it means

Modbus/VERSA error code: HSI Proof.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E43 Modbus/VERSA error code: Low Voltage

What it means

Modbus/VERSA error code: Low Voltage.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E44 Modbus/VERSA error code: Blower Speed

What it means

Modbus/VERSA error code: Blower Speed.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E45 Modbus/VERSA error code: Safety Input

What it means

Modbus/VERSA error code: Safety Input.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E46 Modbus/VERSA error code: Duplicate Master

What it means

Modbus/VERSA error code: Duplicate Master.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E47 Modbus/VERSA error code: Device Error

What it means

Modbus/VERSA error code: Device Error.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E48 Modbus/VERSA error code: Device Lost

What it means

Modbus/VERSA error code: Device Lost.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E49 Modbus/VERSA error code: Supply Sensor / Pool Max Error

What it means

Modbus/VERSA error code: Supply Sensor / Pool Max Error.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E50 Modbus/VERSA error code: MIX Lock Error

What it means

Modbus/VERSA error code: MIX Lock Error.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E51 Modbus/VERSA error code: PIM 2 Ignition Failure

What it means

Modbus/VERSA error code: PIM 2 Ignition Failure.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E52 Modbus/VERSA error code: PIM 2 False Flame

What it means

Modbus/VERSA error code: PIM 2 False Flame.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E53 Modbus/VERSA error code: PIM 2 OEM ID Error

What it means

Modbus/VERSA error code: PIM 2 OEM ID Error.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E54 Modbus/VERSA error code: PIM 2 Internal Failure

What it means

Modbus/VERSA error code: PIM 2 Internal Failure.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E55 Modbus/VERSA error code: PIM 2 HSI Proof

What it means

Modbus/VERSA error code: PIM 2 HSI Proof.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E56 Modbus/VERSA error code: PIM 2 Low Voltage

What it means

Modbus/VERSA error code: PIM 2 Low Voltage.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E57 Modbus/VERSA error code: PIM 2 Blower Speed Flow Read Error

What it means

Modbus/VERSA error code: PIM 2 Blower Speed Flow Read Error.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E58 Modbus/VERSA error code: PIM 2 Safety Input

What it means

Modbus/VERSA error code: PIM 2 Safety Input.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E59 Modbus/VERSA error code: Flow Read Error

What it means

Modbus/VERSA error code: Flow Read Error.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)

E60 Modbus/VERSA error code: Under-Flow Error

What it means

Modbus/VERSA error code: Under-Flow Error.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

E61 Modbus/VERSA error code: Flow Warning

What it means

Modbus/VERSA error code: Flow Warning.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

E62 Modbus/VERSA error code: Device Lost, Cascade Follower # 5

What it means

Modbus/VERSA error code: Device Lost, Cascade Follower # 5.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

E63 Modbus/VERSA error code: Device Lost, Cascade Follower # 6

What it means

Modbus/VERSA error code: Device Lost, Cascade Follower # 6.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

E64 Modbus/VERSA error code: Device Lost, Cascade Follower # 7

What it means

Modbus/VERSA error code: Device Lost, Cascade Follower # 7.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

E65 Modbus/VERSA error code: Device Lost, Cascade Follower # 8

What it means

Modbus/VERSA error code: Device Lost, Cascade Follower # 8.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

E66 Modbus/VERSA error code: Auto Hi-Limit from PIM

What it means

Modbus/VERSA error code: Auto Hi-Limit from PIM.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

E67 Modbus/VERSA error code: Manual Hi-Limit from PIM

What it means

Modbus/VERSA error code: Manual Hi-Limit from PIM.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

E68 Modbus/VERSA error code: Blower Loss from Tach Signal

What it means

Modbus/VERSA error code: Blower Loss from Tach Signal.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

E69 Modbus/VERSA error code: Flame Loss Warning

What it means

Modbus/VERSA error code: Flame Loss Warning.

What to check, in order

The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)

PIM red LED 6 flashes Vent Temperature Fault

Display shows: Red LED – 6 Flashes

What it means

Vent Temperature Fault.

Common causes

What to check, in order

  1. Check for a blocked flue (if a vent sensor is fitted).
  2. Check the vent sensor and wiring
  3. Check vent connections and vent system
  4. If damage is observed, contact a qualified installer to inspect and repair the vent system

When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or venting / flue is a job for a qualified technician.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)

ID CARD Invalid/missing ID card (3-sec delay)

What it means

Invalid/missing ID card (3-sec delay).

Common causes

What to check, in order

  1. Connect the ID card mounted in the heater
  2. If 'Invalid ID Card' is reported, contact the factory.

When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.

Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)

Blue knows every code and the manual for your exact model

Ask Blue free in the Pool AI app: tell Blue the code and your model, and get the steps for your equipment.

Ask Blue free

Pool company? Give your techs Blue: every code, every manual and your customers' equipment in one app.

Give your techs Blue

Questions

What does Raypak code PIM red LED steady on, green power LED off mean on VERSA IC boiler control?

ID Card Fault. First check: Make sure the correct ID card is firmly plugged in.

What does Raypak code PIM red LED steady on mean on VERSA IC boiler control?

Internal Control Fault. First check: Perform a power and system reset.

What does Raypak code PIM red LED 1 flash mean on VERSA IC boiler control?

Airflow Fault. First check: Check blower operation and air flow switch.

What does Raypak code PIM red LED 2 flashes mean on VERSA IC boiler control?

False Flame Error. First check: Check for proper gas valve closure.

What does Raypak code PIM red LED 3 flashes mean on VERSA IC boiler control?

Ignition Lockout Fault. First check: Check the gas supply.

Related

General information from the manufacturers' manuals, written in our own words. Pool AI is not affiliated with or endorsed by the brands named here; brand and model names belong to their owners. Always follow the manual for your exact model and your local codes. Work on gas, high voltage and refrigerant only by qualified, licensed people. Updated 2026-11-23.