Safety first
Gas heater: the gas valve, burners, ignition, flame sensing, venting and anything behind the cabinet panels are for a qualified gas technician. Never jumper or bypass a safety switch or limit. If you smell gas, shut off the gas supply, do not touch electrical switches, leave the area and call your gas company from outside.
Jump to a code
| Code | What it means |
|---|---|
| PIM red LED off | Normal operation |
| PIM red LED steady on, green power LED off | ID Card Fault |
| PIM red LED steady on | Internal Control Fault |
| PIM red LED 1 flash | Airflow Fault |
| PIM red LED 2 flashes | False Flame Error |
| PIM red LED 3 flashes | Ignition Lockout Fault |
| PIM red LED 4 flashes | Ignition Proving Current Fault |
| PIM red LED 5 flashes | Low Voltage Fault: 24VAC input must be above 18.0VAC for proper operation |
| PIM red LED 7 flashes | Hi-Limit Fault |
| PIM red LED 8 flashes | Sensor Fault |
| PIM red LED 9 flashes | No error mode is given for this |
| PIM red LED 10 flashes | Water Pressure Fault |
| PIM red LED 11 flashes | Blower Speed Fault |
| PIM red LED 12 flashes | No error mode is given for this |
| PIM red LED 13 flashes | Hi-Temperature Delta Fault |
| PIM red LED 14 flashes | Ft_bus Communications Fault |
| PIM red LED 15 flashes | General Limit Circuit Fault |
| Primary PIM Fault ID 1 | Hi-Delta only, primary PIM fault: Airflow Fault, triggered by Open or close fault |
| Secondary PIM Fault ID 1 | Hi-Delta only, secondary PIM fault: Airflow Fault, triggered by Open or close fault |
| Primary PIM Fault ID 2 | Hi-Delta only, primary PIM fault: Flame Error, triggered by False flame signal |
| Secondary PIM Fault ID 2 | Hi-Delta only, secondary PIM fault: Flame Error, triggered by False flame signal |
| Primary PIM Fault ID 3 | Hi-Delta only, primary PIM fault: Hard Lockout, triggered by Ignition Lockout |
| Secondary PIM Fault ID 3 | Hi-Delta only, secondary PIM fault: Hard Lockout, triggered by Ignition Lockout |
| Primary PIM Fault ID 4 | Hi-Delta only, primary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in… |
| Secondary PIM Fault ID 4 | Hi-Delta only, secondary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in… |
| Primary PIM Fault ID 5 | Hi-Delta only, primary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac |
| Secondary PIM Fault ID 5 | Hi-Delta only, secondary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac |
| Primary PIM Fault ID 6 | Hi-Delta only, primary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached |
| Secondary PIM Fault ID 6 | Hi-Delta only, secondary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached |
| Primary PIM Fault ID 7 | Hi-Delta only, primary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached |
| Secondary PIM Fault ID 7 | Hi-Delta only, secondary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached |
| Primary PIM Fault ID 9 | Hi-Delta only, primary PIM fault: Safety #1 Fault, triggered by Safety input fault detected |
| Secondary PIM Fault ID 9 | Hi-Delta only, secondary PIM fault: Safety #1 Fault, triggered by Safety input fault detected |
| Primary PIM Fault ID 10 | Hi-Delta only, primary PIM fault: Water flow Fault, triggered by Open or close fault |
| Secondary PIM Fault ID 10 | Hi-Delta only, secondary PIM fault: Water flow Fault, triggered by Open or close fault |
| Primary PIM Fault ID 11 | Hi-Delta only, primary PIM fault: Blower Speed Fault, triggered by RPM out of expected range |
| Secondary PIM Fault ID 11 | Hi-Delta only, secondary PIM fault: Blower Speed Fault, triggered by RPM out of expected range |
| Primary PIM Fault ID 12 | Hi-Delta only, primary PIM fault: LWCO Fault, triggered by LWCO Open |
| Secondary PIM Fault ID 12 | Hi-Delta only, secondary PIM fault: Interlock Fault, triggered by Interlock Open |
| Primary PIM Fault ID 13 | Hi-Delta only, primary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold |
| Secondary PIM Fault ID 13 | Hi-Delta only, secondary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold |
| Primary PIM Fault ID 14 | Hi-Delta only, primary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications |
| Secondary PIM Fault ID 14 | Hi-Delta only, secondary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications |
| Primary PIM Fault ID 15 | Hi-Delta only, primary PIM fault: ID Card Fault, triggered by Invalid or Missing card |
| Secondary PIM Fault ID 15 | Hi-Delta only, secondary PIM fault: ID Card Fault, triggered by Invalid or Missing card |
| Primary PIM Fault ID 16 | Hi-Delta only, primary PIM fault: Outlet Sensor Fault, triggered by Open/short |
| Secondary PIM Fault ID 16 | Hi-Delta only, secondary PIM fault: Outlet Sensor Fault, triggered by Open/short |
| Primary PIM Fault ID 17 | Hi-Delta only, primary PIM fault: Inlet Sensor Fault, triggered by Open/short |
| Secondary PIM Fault ID 17 | Hi-Delta only, secondary PIM fault: Inlet Sensor Fault, triggered by Open/short |
| Primary PIM Fault ID 18 | Hi-Delta only, primary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet |
| Secondary PIM Fault ID 18 | Hi-Delta only, secondary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet |
| Primary PIM Fault ID 19 | Hi-Delta only, primary PIM fault: Vent Sensor Fault, triggered by Open/short |
| Secondary PIM Fault ID 19 | Hi-Delta only, secondary PIM fault: Vent Sensor Fault, triggered by Open/short |
| Primary PIM Fault ID 20 | Hi-Delta only, primary PIM fault: Safety #2 Fault, triggered by Safety input fault detected |
| Secondary PIM Fault ID 20 | Hi-Delta only, secondary PIM fault: Safety #2 Fault, triggered by Safety input fault detected |
| OUTLET SEN | Heater outlet sensor fault (3-sec delay) |
| LIMIT SEN | High limit sensor fault (3-sec delay) |
| INLET SEN | Heater inlet sensor fault (3-sec delay) |
| INTERLOCK | Interlock is open |
| WATER PRESS | Water pressure switch fault (if equipped) |
| AIR PRESS | Air pressure switch fault (if equipped) |
| GAS PRESS | Gas pressure switch fault (if equipped) with a 90-sec delay |
| IGNITION | Ignition fault |
| LIMIT TRIP | Boiler outlet temperature tripped the high limit |
| FLAME | Flame is sensed with no call-for-heat (3-sec delay) |
| IGN CTRL | Internal PIM control fault (3-sec delay) |
| Delta-T | Delta-T temperature went past its threshold (3-sec delay) |
| LO HSI CUR | HSI current is low at the PIM control (3-sec delay) |
| LOW 24VAC | 24VAC power is low at the PIM control (3-sec delay) |
| BLOW SPEED | Blower speed (rpm) is outside its range (3-sec delay) |
| SAFETY INPUT | Additional factory-installed safety fault (3-sec delay) |
| CTRL SETUP | EEPROM setup block could not be read at power-up |
| SUPPLY ERR | System sensor shorted or open |
| DHWSUP ERR | Plant sensor shorted or open |
| OUTDOOR ERR | Outdoor air sensor shorted or open |
| DHW ERR | Indirect DHW sensor shorted or open |
| TANK ERR | Tank sensor shorted or open |
| POOL ERR | Pool sensor shorted or open |
| DEV LOST | Device xx on the heater bus is lost |
| DEV ERR | More than 1 master detected on the tN4 bus (3-sec) |
| PIM 1 ERR | Communication with PIM 1 was working, then dropped (3-sec) |
| PIM 2 ERR | Communication with PIM 2 was working, then dropped (3-sec) |
| PIM 3 ERR | Communication with PIM 3 was working, then dropped (3-sec) |
| PIM 4 ERR | Communication with PIM 4 was working, then dropped (3-sec) |
| CONDENSATE | Condensate switch has tripped (3-sec) |
| VENT TEMP | Vent temperature switch has tripped (1-sec) |
| AUTO LIMIT | Automatic high limit has tripped (3-sec) |
| LOW WATER | Low water cut-off has tripped (1-sec) |
| VENT BLOCK | Blocked vent switch has tripped (3-sec) |
| LOW GAS | Low gas pressure switch has tripped (1-sec) |
| HIGH GAS | High gas pressure switch has tripped (1-sec) |
| EXTRA | Extra limit switch has tripped (1-sec) |
| WATER FLOW | Water flow switch tripped |
| BLOWER | Blower air pressure switch has tripped (10-sec) |
| OPTION 1 | Factory option #1 switch tripped |
| OPTION 2 | Factory option #2 switch tripped |
| OPTION 3 | Factory option #3 switch tripped |
| E0 | Modbus/VERSA error code: No Error |
| E1 | Modbus/VERSA error code: EEPROM Fault |
| E2 | Modbus/VERSA error code: Outdoor Sensor (S4) |
| E3 | Modbus/VERSA error code: System Sensor (S3) |
| E4 | Modbus/VERSA error code: Plant Sensor IND Supply (S6) |
| E5 | Modbus/VERSA error code: Mix Sensor |
| E6 | Modbus/VERSA error code: DHW Sensor (S5) |
| E7 | Modbus/VERSA error code: Tank Sensor |
| E8 | Modbus/VERSA error code: Pool Sensor |
| E9 | Modbus/VERSA error code: No master |
| E10 | Modbus/VERSA error code: No PIM1 |
| E11 | Modbus/VERSA error shown as "Dev Lost / No VRS 2 or No PIM 2" |
| E12 | Modbus/VERSA error shown as "Dev Lost / No VRS 3 or No PIM 3" |
| E13 | Modbus/VERSA error shown as "Dev Lost / No VRS 4 or No PIM 4" |
| E14 | Modbus/VERSA error code: Condensate Switch |
| E15 | Modbus/VERSA error code: Vent Temperature |
| E16 | Modbus/VERSA error code: Auto Hi-Limit |
| E17 | Modbus/VERSA error code: Low Water Cutoff Module |
| E18 | Modbus/VERSA error code: Blocked Vent Switch |
| E19 | Modbus/VERSA error code: Low Gas Pressure |
| E20 | Modbus/VERSA error code: High Gas Pressure |
| E21 | Modbus/VERSA error code: Extra Safety Input |
| E22 | Modbus/VERSA error code: Flow Switch |
| E23 | Modbus/VERSA error code: Air Pressure Switch |
| E24 | Modbus/VERSA error code: Safety Option 1 |
| E25 | Modbus/VERSA error code: Safety Option 2 |
| E26 | Modbus/VERSA error code: Safety Option 3 |
| E27 | Modbus/VERSA error code: LWCO (Jumper) |
| E28 | Modbus/VERSA error code: Water Pressure (Jumper) |
| E29 | Modbus/VERSA error code: Air Pressure (Jumper) |
| E30 | Modbus/VERSA error code: Gas Pressure (Jumper) |
| E31 | Modbus/VERSA error code: Boiler Outlet Sensor |
| E32 | Modbus/VERSA error code: Boiler Inlet Sensor |
| E33 | Modbus/VERSA error code: Vent Sensor |
| E34 | Modbus/VERSA error code: High Limit Sensor (Manual-reset) |
| E35 | Modbus/VERSA error code: Ignition Failure |
| E36 | Modbus/VERSA error code: Vent Hi-Limit |
| E37 | Modbus/VERSA error code: Boiler Hi-Limit |
| E38 | Modbus/VERSA error code: False Flame |
| E39 | Modbus/VERSA error code: OEM ID Card |
| E40 | Modbus/VERSA error code: Internal Fault |
| E41 | Modbus/VERSA error code: Delta-T Max |
| E42 | Modbus/VERSA error code: HSI Proof |
| E43 | Modbus/VERSA error code: Low Voltage |
| E44 | Modbus/VERSA error code: Blower Speed |
| E45 | Modbus/VERSA error code: Safety Input |
| E46 | Modbus/VERSA error code: Duplicate Master |
| E47 | Modbus/VERSA error code: Device Error |
| E48 | Modbus/VERSA error code: Device Lost |
| E49 | Modbus/VERSA error code: Supply Sensor / Pool Max Error |
| E50 | Modbus/VERSA error code: MIX Lock Error |
| E51 | Modbus/VERSA error code: PIM 2 Ignition Failure |
| E52 | Modbus/VERSA error code: PIM 2 False Flame |
| E53 | Modbus/VERSA error code: PIM 2 OEM ID Error |
| E54 | Modbus/VERSA error code: PIM 2 Internal Failure |
| E55 | Modbus/VERSA error code: PIM 2 HSI Proof |
| E56 | Modbus/VERSA error code: PIM 2 Low Voltage |
| E57 | Modbus/VERSA error code: PIM 2 Blower Speed Flow Read Error |
| E58 | Modbus/VERSA error code: PIM 2 Safety Input |
| E59 | Modbus/VERSA error code: Flow Read Error |
| E60 | Modbus/VERSA error code: Under-Flow Error |
| E61 | Modbus/VERSA error code: Flow Warning |
| E62 | Modbus/VERSA error code: Device Lost, Cascade Follower # 5 |
| E63 | Modbus/VERSA error code: Device Lost, Cascade Follower # 6 |
| E64 | Modbus/VERSA error code: Device Lost, Cascade Follower # 7 |
| E65 | Modbus/VERSA error code: Device Lost, Cascade Follower # 8 |
| E66 | Modbus/VERSA error code: Auto Hi-Limit from PIM |
| E67 | Modbus/VERSA error code: Manual Hi-Limit from PIM |
| E68 | Modbus/VERSA error code: Blower Loss from Tach Signal |
| E69 | Modbus/VERSA error code: Flame Loss Warning |
| PIM red LED 6 flashes | Vent Temperature Fault |
| ID CARD | Invalid/missing ID card (3-sec delay) |
PIM red LED off Normal operation
Display shows: Red LED OFF
What it means
Normal operation.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED steady on, green power LED off ID Card Fault
Display shows: Red LED Steady ON, Green Power LED OFF
What it means
ID Card Fault.
Common causes
- ID card missing, wrong or not securely connected
What to check, in order
- Make sure the correct ID card is firmly plugged in.
- Perform a power and system reset
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED steady on Internal Control Fault
Display shows: Red LED Steady ON
What it means
Internal Control Fault.
Common causes
- PIM internal control fault
What to check, in order
- Perform a power and system reset
- If the fault remains, replace the PIM
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 1 flash Airflow Fault
Display shows: Red LED – 1 Flash
What it means
Airflow Fault.
Common causes
- Airflow fault
What to check, in order
- Check blower operation and air flow switch
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 2 flashes False Flame Error
Display shows: Red LED – 2 Flashes
What it means
False Flame Error.
Common causes
- False flame signal
What to check, in order
- Check for proper gas valve closure
- Clean burner and electrodes
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the gas valve or burners is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 3 flashes Ignition Lockout Fault
Display shows: Red LED – 3 Flashes
What it means
Ignition Lockout Fault.
Common causes
- Ignition lockout
What to check, in order
- Check the gas supply
- Check transformer
- Check igniters
- Check wiring
- Press the reset button on the PIM/membrane switch
- Recycle power
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control, wiring, electrical parts (fuses, relays, transformers) or gas supply and pressure is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 4 flashes Ignition Proving Current Fault
Display shows: Red LED – 4 Flashes
What it means
Ignition Proving Current Fault.
Common causes
- Hot surface igniter (HSI) current fault
What to check, in order
- Check the HSI element (models with a hot surface igniter)
- Replace as necessary
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 5 flashes Low Voltage Fault: 24VAC input must be above 18.0VAC for proper operation
Display shows: Red LED – 5 Flashes
What it means
Low Voltage Fault: 24VAC input must be above 18.0VAC for proper operation.
Common causes
- 24VAC input at or below 18.0VAC
What to check, in order
- Check the 24VAC input voltage (must be above 18.0VAC)
- Replace transformer as necessary
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage or electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 7 flashes Hi-Limit Fault
Display shows: Red LED – 7 Flashes
What it means
Hi-Limit Fault.
Common causes
- High limit reached
What to check, in order
- Check for proper water flow
- Check hi-limit setting and outlet sensor
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 8 flashes Sensor Fault
Display shows: Red LED – 8 Flashes
What it means
Sensor Fault.
Common causes
- Sensor fault
What to check, in order
- Check the VERSA IC for fault identification
- Check sensor and wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 9 flashes No error mode is given for this
Display shows: Red LED – 9 Flashes
What it means
No error mode is given for this; check the wiring.
What to check, in order
- At J8, pins 1 and 3, the wiring should be checked for a missing or loose jumper.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 10 flashes Water Pressure Fault
Display shows: Red LED – 10 Flashes
What it means
Water Pressure Fault.
Common causes
- Water pressure fault
What to check, in order
- Check system piping for leaks
- Check the water pressure switch (if equipped) and connections
- On the PIM, J1 pins 6 and 7: check the wiring for a missing or loose jumper.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 11 flashes Blower Speed Fault
Display shows: Red LED – 11 Flashes
What it means
Blower Speed Fault.
Common causes
- Blower speed fault
What to check, in order
- Confirm the tachometer signal and connections at terminals J10 on the PIM.
- Confirm power to the boiler is at or above the minimum required
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 12 flashes No error mode is given for this
Display shows: Red LED – 12 Flashes
What it means
No error mode is given for this; check the wiring.
What to check, in order
- On the PIM, J1 pins 3 and 4: check the wiring for a missing or loose jumper.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 13 flashes Hi-Temperature Delta Fault
Display shows: Red LED – 13 Flashes
What it means
Hi-Temperature Delta Fault.
Common causes
- Temperature rise (Delta-T) too high
What to check, in order
- Check pump operation
- Confirm proper water flow across the heat exchanger (Delta-T)
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 14 flashes Ft_bus Communications Fault
Display shows: Red LED – 14 Flashes
What it means
Ft_bus Communications Fault.
Common causes
- Communication lost between PIM and VERSA IC
What to check, in order
- Confirm the VERSA IC is connected and working correctly.
- Inspect the cable that runs between the PIM and the VERSA IC.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
PIM red LED 15 flashes General Limit Circuit Fault
Display shows: Red LED – 15 Flashes
What it means
General Limit Circuit Fault.
Common causes
- Limit circuit fault
What to check, in order
- Look at the VERSA IC for fault indications and troubleshooting details.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
Primary PIM Fault ID 1 Hi-Delta only, primary PIM fault: Airflow Fault, triggered by Open or close fault
Display shows: Fault ID 1
What it means
Hi-Delta only, primary PIM fault: Airflow Fault, triggered by Open or close fault. LED blinks 1 time. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Open or close fault
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 1 Hi-Delta only, secondary PIM fault: Airflow Fault, triggered by Open or close fault
Display shows: Fault ID 1
What it means
Hi-Delta only, secondary PIM fault: Airflow Fault, triggered by Open or close fault. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Open or close fault
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 2 Hi-Delta only, primary PIM fault: Flame Error, triggered by False flame signal
Display shows: Fault ID 2
What it means
Hi-Delta only, primary PIM fault: Flame Error, triggered by False flame signal. LED blinks 2 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- False flame signal
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 2 Hi-Delta only, secondary PIM fault: Flame Error, triggered by False flame signal
Display shows: Fault ID 2
What it means
Hi-Delta only, secondary PIM fault: Flame Error, triggered by False flame signal. LED blinks 2 times. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- False flame signal
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 3 Hi-Delta only, primary PIM fault: Hard Lockout, triggered by Ignition Lockout
Display shows: Fault ID 3
What it means
Hi-Delta only, primary PIM fault: Hard Lockout, triggered by Ignition Lockout. LED blinks 3 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Ignition Lockout
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 3 Hi-Delta only, secondary PIM fault: Hard Lockout, triggered by Ignition Lockout
Display shows: Fault ID 3
What it means
Hi-Delta only, secondary PIM fault: Hard Lockout, triggered by Ignition Lockout. LED blinks 3 times. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Ignition Lockout
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 4 Hi-Delta only, primary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in…
Display shows: Fault ID 4
What it means
Hi-Delta only, primary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in range. LED blinks 4 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- HSI Element current not in range
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 4 Hi-Delta only, secondary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in…
Display shows: Fault ID 4
What it means
Hi-Delta only, secondary PIM fault: Ignition Proving Current fault, triggered by HSI Element current not in range. LED blinks 4 times. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- HSI Element current not in range
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control or electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 5 Hi-Delta only, primary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac
Display shows: Fault ID 5
What it means
Hi-Delta only, primary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac. LED blinks 5 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Voltage below 18.0Vac
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage or electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 5 Hi-Delta only, secondary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac
Display shows: Fault ID 5
What it means
Hi-Delta only, secondary PIM fault: Low Voltage Fault, triggered by Voltage below 18.0Vac. LED blinks 5 times. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Voltage below 18.0Vac
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage or electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 6 Hi-Delta only, primary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached
Display shows: Fault ID 6
What it means
Hi-Delta only, primary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached. LED blinks 6 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- High Vent temperature reached
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) or venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 6 Hi-Delta only, secondary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached
Display shows: Fault ID 6
What it means
Hi-Delta only, secondary PIM fault: Vent Temperature Fault, triggered by High Vent temperature reached. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- High Vent temperature reached
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) or venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 7 Hi-Delta only, primary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached
Display shows: Fault ID 7
What it means
Hi-Delta only, primary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached. LED blinks 7 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Hi-Limit Reached
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 7 Hi-Delta only, secondary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached
Display shows: Fault ID 7
What it means
Hi-Delta only, secondary PIM fault: Hi-Limit Fault, triggered by Hi-Limit Reached. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Hi-Limit Reached
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 9 Hi-Delta only, primary PIM fault: Safety #1 Fault, triggered by Safety input fault detected
Display shows: Fault ID 9
What it means
Hi-Delta only, primary PIM fault: Safety #1 Fault, triggered by Safety input fault detected. LED blinks 9 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Safety input fault detected
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 9 Hi-Delta only, secondary PIM fault: Safety #1 Fault, triggered by Safety input fault detected
Display shows: Fault ID 9
What it means
Hi-Delta only, secondary PIM fault: Safety #1 Fault, triggered by Safety input fault detected. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Safety input fault detected
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 10 Hi-Delta only, primary PIM fault: Water flow Fault, triggered by Open or close fault
Display shows: Fault ID 10
What it means
Hi-Delta only, primary PIM fault: Water flow Fault, triggered by Open or close fault. LED blinks 10 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Open or close fault
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 10 Hi-Delta only, secondary PIM fault: Water flow Fault, triggered by Open or close fault
Display shows: Fault ID 10
What it means
Hi-Delta only, secondary PIM fault: Water flow Fault, triggered by Open or close fault. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Open or close fault
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 11 Hi-Delta only, primary PIM fault: Blower Speed Fault, triggered by RPM out of expected range
Display shows: Fault ID 11
What it means
Hi-Delta only, primary PIM fault: Blower Speed Fault, triggered by RPM out of expected range. LED blinks 11 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- RPM out of expected range
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 11 Hi-Delta only, secondary PIM fault: Blower Speed Fault, triggered by RPM out of expected range
Display shows: Fault ID 11
What it means
Hi-Delta only, secondary PIM fault: Blower Speed Fault, triggered by RPM out of expected range. LED blinks 11 times. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- RPM out of expected range
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 12 Hi-Delta only, primary PIM fault: LWCO Fault, triggered by LWCO Open
Display shows: Fault ID 12
What it means
Hi-Delta only, primary PIM fault: LWCO Fault, triggered by LWCO Open. LED blinks 12 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- LWCO Open
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 12 Hi-Delta only, secondary PIM fault: Interlock Fault, triggered by Interlock Open
Display shows: Fault ID 12
What it means
Hi-Delta only, secondary PIM fault: Interlock Fault, triggered by Interlock Open. LED blinks 12 times. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Interlock Open
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 13 Hi-Delta only, primary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold
Display shows: Fault ID 13
What it means
Hi-Delta only, primary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold. LED blinks 13 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Delta-T exceeds threshold
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 13 Hi-Delta only, secondary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold
Display shows: Fault ID 13
What it means
Hi-Delta only, secondary PIM fault: Hi-Delta-Temp Fault, triggered by Delta-T exceeds threshold. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Delta-T exceeds threshold
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 14 Hi-Delta only, primary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications
Display shows: Fault ID 14
What it means
Hi-Delta only, primary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications. LED blinks 14 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Loss of Communications
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 14 Hi-Delta only, secondary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications
Display shows: Fault ID 14
What it means
Hi-Delta only, secondary PIM fault: Ft_Bus Comm Fault, triggered by Loss of Communications. LED blinks 14 times. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Loss of Communications
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 15 Hi-Delta only, primary PIM fault: ID Card Fault, triggered by Invalid or Missing card
Display shows: Fault ID 15
What it means
Hi-Delta only, primary PIM fault: ID Card Fault, triggered by Invalid or Missing card. LED shows red on, green off. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Invalid or Missing card
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 15 Hi-Delta only, secondary PIM fault: ID Card Fault, triggered by Invalid or Missing card
Display shows: Fault ID 15
What it means
Hi-Delta only, secondary PIM fault: ID Card Fault, triggered by Invalid or Missing card. LED shows red on, green off. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Invalid or Missing card
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 16 Hi-Delta only, primary PIM fault: Outlet Sensor Fault, triggered by Open/short
Display shows: Fault ID 16
What it means
Hi-Delta only, primary PIM fault: Outlet Sensor Fault, triggered by Open/short. LED blinks 8 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Open/short
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 16 Hi-Delta only, secondary PIM fault: Outlet Sensor Fault, triggered by Open/short
Display shows: Fault ID 16
What it means
Hi-Delta only, secondary PIM fault: Outlet Sensor Fault, triggered by Open/short. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Open/short
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 17 Hi-Delta only, primary PIM fault: Inlet Sensor Fault, triggered by Open/short
Display shows: Fault ID 17
What it means
Hi-Delta only, primary PIM fault: Inlet Sensor Fault, triggered by Open/short. LED blinks 8 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Open/short
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 17 Hi-Delta only, secondary PIM fault: Inlet Sensor Fault, triggered by Open/short
Display shows: Fault ID 17
What it means
Hi-Delta only, secondary PIM fault: Inlet Sensor Fault, triggered by Open/short. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Open/short
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 18 Hi-Delta only, primary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet
Display shows: Fault ID 18
What it means
Hi-Delta only, primary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet. LED blinks 8 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Open/short or mismatch to outlet
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 18 Hi-Delta only, secondary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet
Display shows: Fault ID 18
What it means
Hi-Delta only, secondary PIM fault: Hi-Limit Sensor Fault, triggered by Open/short or mismatch to outlet. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Open/short or mismatch to outlet
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 19 Hi-Delta only, primary PIM fault: Vent Sensor Fault, triggered by Open/short
Display shows: Fault ID 19
What it means
Hi-Delta only, primary PIM fault: Vent Sensor Fault, triggered by Open/short. LED blinks 8 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Open/short
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) or venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 19 Hi-Delta only, secondary PIM fault: Vent Sensor Fault, triggered by Open/short
Display shows: Fault ID 19
What it means
Hi-Delta only, secondary PIM fault: Vent Sensor Fault, triggered by Open/short. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Open/short
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) or venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Primary PIM Fault ID 20 Hi-Delta only, primary PIM fault: Safety #2 Fault, triggered by Safety input fault detected
Display shows: Fault ID 20
What it means
Hi-Delta only, primary PIM fault: Safety #2 Fault, triggered by Safety input fault detected. LED blinks 15 times. The secondary PIM tracks the primary PIM's fault status and powers the alarm relay.
Common causes
- Safety input fault detected
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
Secondary PIM Fault ID 20 Hi-Delta only, secondary PIM fault: Safety #2 Fault, triggered by Safety input fault detected
Display shows: Fault ID 20
What it means
Hi-Delta only, secondary PIM fault: Safety #2 Fault, triggered by Safety input fault detected. The secondary PIM has no LED code. The secondary PIM powers the alarm relay for any Fault ID shown.
Common causes
- Safety input fault detected
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 69. maker's manual (PDF)
OUTLET SEN Heater outlet sensor fault (3-sec delay)
What it means
Heater outlet sensor fault (3-sec delay).
Common causes
- Outlet sensor or wiring fault
What to check, in order
- Check outlet sensor
- Check outlet sensor wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
LIMIT SEN High limit sensor fault (3-sec delay)
What it means
High limit sensor fault (3-sec delay).
Common causes
- High limit sensor or wiring fault
What to check, in order
- Check limit sensor
- Check limit sensor wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
INLET SEN Heater inlet sensor fault (3-sec delay)
What it means
Heater inlet sensor fault (3-sec delay).
Common causes
- Inlet sensor or wiring fault
What to check, in order
- Check inlet sensor
- Check inlet sensor wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
INTERLOCK Interlock is open
What it means
Interlock is open; a jumper installed at the factory is in place on shipment (90-sec delay).
Common causes
- Louver end switch, combustion air damper end switch or extractor open
What to check, in order
- Check louver end switch and wiring
- Check combustion air damper end switch and wiring
- Check extractor and wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
WATER PRESS Water pressure switch fault (if equipped)
What it means
Water pressure switch fault (if equipped); factory jumper in place if not shipped with a water pressure switch (90-sec delay).
Common causes
- Water pressure switch open
What to check, in order
- Verify wiring at J1 terminals 6 & 7
- Check heater pump
- Check isolation valves
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
AIR PRESS Air pressure switch fault (if equipped)
What it means
Air pressure switch fault (if equipped); factory jumper in place if not shipped with an air pressure switch (90-sec delay).
Common causes
- Air pressure switch open
What to check, in order
- Verify wiring at J8 terminals 2 & 4
- Check blower(s)
- Check air pressure switch tubing
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
GAS PRESS Gas pressure switch fault (if equipped) with a 90-sec delay
What it means
Gas pressure switch fault (if equipped) with a 90-sec delay. A factory jumper is in place when the unit ships without a high and/or low gas pressure switch.
Common causes
- Gas pressure switch open
What to check, in order
- Verify wiring at J8 terminals 1 & 3
- Check gas pressure switches
- Check gas pressure
- Check gas pressure switch tubing
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or gas supply and pressure is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
IGNITION Ignition fault
What it means
Ignition fault.
Common causes
- Ignition fault
What to check, in order
- Reset the ignition control: push either RESET button on the membrane switch or the reset button on the PIM, or recycle power
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
LIMIT TRIP Boiler outlet temperature tripped the high limit
What it means
Boiler outlet temperature tripped the high limit.
Common causes
- Outlet temperature reached the high limit
What to check, in order
- If the manual-reset high limit tripped, press the reset button on the high limit control.
- Wait for water temperature to drop; the auto-reset high limit will reset
- Check pump operation
- Look for too much water flow through the bypass (if fitted).
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
FLAME Flame is sensed with no call-for-heat (3-sec delay)
What it means
Flame is sensed with no call-for-heat (3-sec delay).
Common causes
- Flame without call for heat
What to check, in order
- Shut off the gas supply
- Recycle power
- Check gas valve leakage
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the gas valve or gas supply and pressure is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
IGN CTRL Internal PIM control fault (3-sec delay)
What it means
Internal PIM control fault (3-sec delay).
Common causes
- Internal PIM control fault
What to check, in order
- Recycle power
- If the error continues, replace the PIM
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
Delta-T Delta-T temperature went past its threshold (3-sec delay)
What it means
Delta-T temperature went past its threshold (3-sec delay).
Common causes
- Delta-T threshold exceeded
What to check, in order
- Check pump operation
- Check Delta-T setting
- Look for too much water flow through the bypass (if fitted).
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
LO HSI CUR HSI current is low at the PIM control (3-sec delay)
What it means
HSI current is low at the PIM control (3-sec delay).
Common causes
- Low hot surface igniter current
What to check, in order
- Check HSI current
- Replace HSI
- Replace PIM control
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
LOW 24VAC 24VAC power is low at the PIM control (3-sec delay)
What it means
24VAC power is low at the PIM control (3-sec delay).
Common causes
- Low 24VAC supply
What to check, in order
- Check power supply
- Check transformer
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage or electrical parts (fuses, relays, transformers) is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
BLOW SPEED Blower speed (rpm) is outside its range (3-sec delay)
What it means
Blower speed (rpm) is outside its range (3-sec delay).
Common causes
- Blower speed out of range
What to check, in order
- Check power supply
- Check blower wiring to PIM
- Check blower type
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
SAFETY INPUT Additional factory-installed safety fault (3-sec delay)
What it means
Additional factory-installed safety fault (3-sec delay); see the product installation and operation manual.
Common causes
- Additional factory safety input open
What to check, in order
- Verify wiring at J8 terminals 5 & 6
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
CTRL SETUP EEPROM setup block could not be read at power-up
What it means
EEPROM setup block could not be read at power-up; factory defaults were reloaded and operation halts until every adjustment is verified (3-sec timeout).
Common causes
- EEPROM setup read error
What to check, in order
- Go through all SETUP items; resetting the VERSA to factory defaults may clear these faults.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
SUPPLY ERR System sensor shorted or open
What it means
System sensor shorted or open; the control will cease operation (3-sec).
Common causes
- System sensor (S3) shorted or open
What to check, in order
- Check System sensor (S3)
- Check System sensor (S3) wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
DHWSUP ERR Plant sensor shorted or open
What it means
Plant sensor shorted or open; the control will cease operation (3-sec).
Common causes
- Plant (Aux1) sensor shorted or open
What to check, in order
- Check Aux1 sensor
- Check Aux 1 sensor wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
OUTDOOR ERR Outdoor air sensor shorted or open
What it means
Outdoor air sensor shorted or open; control keeps operating assuming 32°F (0°C) outdoor (3-sec). 15 min soft lockout.
Common causes
- Outdoor air sensor shorted or open
What to check, in order
- Check outdoor air sensor
- Check outdoor air sensor wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
DHW ERR Indirect DHW sensor shorted or open
What it means
Indirect DHW sensor shorted or open; indirect DHW stops but system heating continues (3-sec).
Common causes
- Indirect DHW sensor shorted or open
What to check, in order
- Check DHW sensor
- Check DHW sensor wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
TANK ERR Tank sensor shorted or open
What it means
Tank sensor shorted or open; the control will cease operation (3-sec).
Common causes
- Tank sensor shorted or open
What to check, in order
- Check tank sensor
- Check tank sensor wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
POOL ERR Pool sensor shorted or open
What it means
Pool sensor shorted or open; the control will cease operation (3-sec).
Common causes
- Pool sensor shorted or open
What to check, in order
- Check pool sensor
- Check pool sensor wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
DEV LOST Device xx on the heater bus is lost
What it means
Device xx on the heater bus is lost; if on the tN4 bus the zone is shown too (3-sec).
Common causes
- Device lost on heater bus
What to check, in order
- Check wiring between the VERSA IC board and all PIMs on the network
- Check communication wiring for the BMS system
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
DEV ERR More than 1 master detected on the tN4 bus (3-sec)
What it means
More than 1 master detected on the tN4 bus (3-sec).
Common causes
- More than one master on tN4 bus
What to check, in order
- Check DIP switches on cascaded heaters so only 1 unit is Master and the others Followers/Slave
- Check communication wiring at the heater with the noted address
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
PIM 1 ERR Communication with PIM 1 was working, then dropped (3-sec)
What it means
Communication with PIM 1 was working, then dropped (3-sec).
Common causes
- Lost communication with PIM 1
What to check, in order
- Inspect the cabling and the DIP switch settings for the Master/Follower setup.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
PIM 2 ERR Communication with PIM 2 was working, then dropped (3-sec)
What it means
Communication with PIM 2 was working, then dropped (3-sec).
Common causes
- Lost communication with PIM 2
What to check, in order
- Confirm cabling and DIP switch settings
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
PIM 3 ERR Communication with PIM 3 was working, then dropped (3-sec)
What it means
Communication with PIM 3 was working, then dropped (3-sec).
Common causes
- Lost communication with PIM 3
What to check, in order
- Confirm cabling and DIP switch settings
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
PIM 4 ERR Communication with PIM 4 was working, then dropped (3-sec)
What it means
Communication with PIM 4 was working, then dropped (3-sec).
Common causes
- Lost communication with PIM 4
What to check, in order
- Confirm cabling and DIP switch settings
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
CONDENSATE Condensate switch has tripped (3-sec)
What it means
Condensate switch has tripped (3-sec). 15 min soft lockout.
Common causes
- Condensate switch tripped
What to check, in order
- Check for blockage of condensate drain
- Check condensate switch
- Check condensate switch wiring
- Check for a heat exchanger leak that may overwhelm the condensate drain
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
VENT TEMP Vent temperature switch has tripped (1-sec)
What it means
Vent temperature switch has tripped (1-sec).
Common causes
- Vent temperature switch tripped
What to check, in order
- Check vent temperature switch
- Check vent temperature switch wiring
- Check PVC/CPVC/Polypropylene vent for damage from excessive temperatures
- Check vent for leaks near the vent temperature switch
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
AUTO LIMIT Automatic high limit has tripped (3-sec)
What it means
Automatic high limit has tripped (3-sec). 15 min soft lockout.
Common causes
- Automatic high limit tripped
What to check, in order
- Check the automatic high limit switch
- Check the automatic high limit switch wiring
- Check for proper pump operation
- Look for too much water flow through the bypass (if fitted).
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
LOW WATER Low water cut-off has tripped (1-sec)
What it means
Low water cut-off has tripped (1-sec).
Common causes
- Low water cut-off tripped
What to check, in order
- Push the reset button on the LWCO control
- Check LWCO probe and wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
VENT BLOCK Blocked vent switch has tripped (3-sec)
What it means
Blocked vent switch has tripped (3-sec). 15 min soft lockout.
Common causes
- Blocked vent switch tripped
What to check, in order
- Check venting
- Check vent pressure switch and wiring
- Check vent pressure switch tubing
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
LOW GAS Low gas pressure switch has tripped (1-sec)
What it means
Low gas pressure switch has tripped (1-sec).
Common causes
- Low gas pressure
What to check, in order
- Push the reset button on the low gas pressure switch
- Verify proper gas pressure
- Open manual gas valves fully
- Clean out drip leg
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the gas valve or gas supply and pressure is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
HIGH GAS High gas pressure switch has tripped (1-sec)
What it means
High gas pressure switch has tripped (1-sec).
Common causes
- High gas pressure
What to check, in order
- Push the reset button on the high gas pressure switch
- Verify proper gas pressures
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
EXTRA Extra limit switch has tripped (1-sec)
What it means
Extra limit switch has tripped (1-sec); see the product installation and operation manual for this limit.
Common causes
- Extra limit switch tripped
What to check, in order
- Refer to the troubleshooting section of the installation and operation instructions for this specific product.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
WATER FLOW Water flow switch tripped
What it means
Water flow switch tripped. It takes 10-sec to close, then 1-sec to reach 'FAULT' (3-sec). Soft lockout lasts 15 min.
Common causes
- Water flow switch tripped
What to check, in order
- Check heater pump operation
- Purge air from system
- Replace flow switch as necessary
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
BLOWER Blower air pressure switch has tripped (10-sec)
What it means
Blower air pressure switch has tripped (10-sec). 15 min soft lockout.
Common causes
- Blower air pressure switch tripped
What to check, in order
- Check air filter
- Check blower
- Check air pressure switch hose
- Check wiring
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
OPTION 1 Factory option #1 switch tripped
What it means
Factory option #1 switch tripped; the fault is reported only after a 10-sec delay on the first CFH.
Common causes
- Factory option #1 switch tripped
What to check, in order
- See the wiring diagram to find out what is connected here.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
OPTION 2 Factory option #2 switch tripped
What it means
Factory option #2 switch tripped; the fault is reported only after a 30-sec delay on the first CFH.
Common causes
- Factory option #2 switch tripped
What to check, in order
- See the wiring diagram to find out what is connected here.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
OPTION 3 Factory option #3 switch tripped
What it means
Factory option #3 switch tripped; the fault is reported only after a 90-sec delay on the first CFH.
Common causes
- Factory option #3 switch tripped
What to check, in order
- See the wiring diagram to find out what is connected here.
- Inspect field interlocks, for example the combustion air damper proving switch.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 71. maker's manual (PDF)
E0 Modbus/VERSA error code: No Error
What it means
Modbus/VERSA error code: No Error.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E1 Modbus/VERSA error code: EEPROM Fault
What it means
Modbus/VERSA error code: EEPROM Fault.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E2 Modbus/VERSA error code: Outdoor Sensor (S4)
What it means
Modbus/VERSA error code: Outdoor Sensor (S4).
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E3 Modbus/VERSA error code: System Sensor (S3)
What it means
Modbus/VERSA error code: System Sensor (S3).
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E4 Modbus/VERSA error code: Plant Sensor IND Supply (S6)
What it means
Modbus/VERSA error code: Plant Sensor IND Supply (S6).
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E5 Modbus/VERSA error code: Mix Sensor
What it means
Modbus/VERSA error code: Mix Sensor.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E6 Modbus/VERSA error code: DHW Sensor (S5)
What it means
Modbus/VERSA error code: DHW Sensor (S5).
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E7 Modbus/VERSA error code: Tank Sensor
What it means
Modbus/VERSA error code: Tank Sensor.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E8 Modbus/VERSA error code: Pool Sensor
What it means
Modbus/VERSA error code: Pool Sensor.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E9 Modbus/VERSA error code: No master
What it means
Modbus/VERSA error code: No master.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E10 Modbus/VERSA error code: No PIM1
What it means
Modbus/VERSA error code: No PIM1.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E11 Modbus/VERSA error shown as "Dev Lost / No VRS 2 or No PIM 2"
What it means
Modbus/VERSA error shown as "Dev Lost / No VRS 2 or No PIM 2".
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E12 Modbus/VERSA error shown as "Dev Lost / No VRS 3 or No PIM 3"
What it means
Modbus/VERSA error shown as "Dev Lost / No VRS 3 or No PIM 3".
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E13 Modbus/VERSA error shown as "Dev Lost / No VRS 4 or No PIM 4"
What it means
Modbus/VERSA error shown as "Dev Lost / No VRS 4 or No PIM 4".
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E14 Modbus/VERSA error code: Condensate Switch
What it means
Modbus/VERSA error code: Condensate Switch.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E15 Modbus/VERSA error code: Vent Temperature
What it means
Modbus/VERSA error code: Vent Temperature.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E16 Modbus/VERSA error code: Auto Hi-Limit
What it means
Modbus/VERSA error code: Auto Hi-Limit.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E17 Modbus/VERSA error code: Low Water Cutoff Module
What it means
Modbus/VERSA error code: Low Water Cutoff Module.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E18 Modbus/VERSA error code: Blocked Vent Switch
What it means
Modbus/VERSA error code: Blocked Vent Switch.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E19 Modbus/VERSA error code: Low Gas Pressure
What it means
Modbus/VERSA error code: Low Gas Pressure.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E20 Modbus/VERSA error code: High Gas Pressure
What it means
Modbus/VERSA error code: High Gas Pressure.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E21 Modbus/VERSA error code: Extra Safety Input
What it means
Modbus/VERSA error code: Extra Safety Input.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E22 Modbus/VERSA error code: Flow Switch
What it means
Modbus/VERSA error code: Flow Switch.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E23 Modbus/VERSA error code: Air Pressure Switch
What it means
Modbus/VERSA error code: Air Pressure Switch.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E24 Modbus/VERSA error code: Safety Option 1
What it means
Modbus/VERSA error code: Safety Option 1.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E25 Modbus/VERSA error code: Safety Option 2
What it means
Modbus/VERSA error code: Safety Option 2.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E26 Modbus/VERSA error code: Safety Option 3
What it means
Modbus/VERSA error code: Safety Option 3.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E27 Modbus/VERSA error code: LWCO (Jumper)
What it means
Modbus/VERSA error code: LWCO (Jumper).
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E28 Modbus/VERSA error code: Water Pressure (Jumper)
What it means
Modbus/VERSA error code: Water Pressure (Jumper).
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E29 Modbus/VERSA error code: Air Pressure (Jumper)
What it means
Modbus/VERSA error code: Air Pressure (Jumper).
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E30 Modbus/VERSA error code: Gas Pressure (Jumper)
What it means
Modbus/VERSA error code: Gas Pressure (Jumper).
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving gas supply and pressure is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E31 Modbus/VERSA error code: Boiler Outlet Sensor
What it means
Modbus/VERSA error code: Boiler Outlet Sensor.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E32 Modbus/VERSA error code: Boiler Inlet Sensor
What it means
Modbus/VERSA error code: Boiler Inlet Sensor.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E33 Modbus/VERSA error code: Vent Sensor
What it means
Modbus/VERSA error code: Vent Sensor.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E34 Modbus/VERSA error code: High Limit Sensor (Manual-reset)
What it means
Modbus/VERSA error code: High Limit Sensor (Manual-reset).
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E35 Modbus/VERSA error code: Ignition Failure
What it means
Modbus/VERSA error code: Ignition Failure.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E36 Modbus/VERSA error code: Vent Hi-Limit
What it means
Modbus/VERSA error code: Vent Hi-Limit.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E37 Modbus/VERSA error code: Boiler Hi-Limit
What it means
Modbus/VERSA error code: Boiler Hi-Limit.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E38 Modbus/VERSA error code: False Flame
What it means
Modbus/VERSA error code: False Flame.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E39 Modbus/VERSA error code: OEM ID Card
What it means
Modbus/VERSA error code: OEM ID Card.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E40 Modbus/VERSA error code: Internal Fault
What it means
Modbus/VERSA error code: Internal Fault.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E41 Modbus/VERSA error code: Delta-T Max
What it means
Modbus/VERSA error code: Delta-T Max.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E42 Modbus/VERSA error code: HSI Proof
What it means
Modbus/VERSA error code: HSI Proof.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E43 Modbus/VERSA error code: Low Voltage
What it means
Modbus/VERSA error code: Low Voltage.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E44 Modbus/VERSA error code: Blower Speed
What it means
Modbus/VERSA error code: Blower Speed.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E45 Modbus/VERSA error code: Safety Input
What it means
Modbus/VERSA error code: Safety Input.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E46 Modbus/VERSA error code: Duplicate Master
What it means
Modbus/VERSA error code: Duplicate Master.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E47 Modbus/VERSA error code: Device Error
What it means
Modbus/VERSA error code: Device Error.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E48 Modbus/VERSA error code: Device Lost
What it means
Modbus/VERSA error code: Device Lost.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E49 Modbus/VERSA error code: Supply Sensor / Pool Max Error
What it means
Modbus/VERSA error code: Supply Sensor / Pool Max Error.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E50 Modbus/VERSA error code: MIX Lock Error
What it means
Modbus/VERSA error code: MIX Lock Error.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E51 Modbus/VERSA error code: PIM 2 Ignition Failure
What it means
Modbus/VERSA error code: PIM 2 Ignition Failure.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving the igniter or ignition control is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E52 Modbus/VERSA error code: PIM 2 False Flame
What it means
Modbus/VERSA error code: PIM 2 False Flame.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E53 Modbus/VERSA error code: PIM 2 OEM ID Error
What it means
Modbus/VERSA error code: PIM 2 OEM ID Error.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E54 Modbus/VERSA error code: PIM 2 Internal Failure
What it means
Modbus/VERSA error code: PIM 2 Internal Failure.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E55 Modbus/VERSA error code: PIM 2 HSI Proof
What it means
Modbus/VERSA error code: PIM 2 HSI Proof.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E56 Modbus/VERSA error code: PIM 2 Low Voltage
What it means
Modbus/VERSA error code: PIM 2 Low Voltage.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving measuring voltage is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E57 Modbus/VERSA error code: PIM 2 Blower Speed Flow Read Error
What it means
Modbus/VERSA error code: PIM 2 Blower Speed Flow Read Error.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E58 Modbus/VERSA error code: PIM 2 Safety Input
What it means
Modbus/VERSA error code: PIM 2 Safety Input.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E59 Modbus/VERSA error code: Flow Read Error
What it means
Modbus/VERSA error code: Flow Read Error.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 84. maker's manual (PDF)
E60 Modbus/VERSA error code: Under-Flow Error
What it means
Modbus/VERSA error code: Under-Flow Error.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
E61 Modbus/VERSA error code: Flow Warning
What it means
Modbus/VERSA error code: Flow Warning.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
E62 Modbus/VERSA error code: Device Lost, Cascade Follower # 5
What it means
Modbus/VERSA error code: Device Lost, Cascade Follower # 5.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
E63 Modbus/VERSA error code: Device Lost, Cascade Follower # 6
What it means
Modbus/VERSA error code: Device Lost, Cascade Follower # 6.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
E64 Modbus/VERSA error code: Device Lost, Cascade Follower # 7
What it means
Modbus/VERSA error code: Device Lost, Cascade Follower # 7.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
E65 Modbus/VERSA error code: Device Lost, Cascade Follower # 8
What it means
Modbus/VERSA error code: Device Lost, Cascade Follower # 8.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
E66 Modbus/VERSA error code: Auto Hi-Limit from PIM
What it means
Modbus/VERSA error code: Auto Hi-Limit from PIM.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
E67 Modbus/VERSA error code: Manual Hi-Limit from PIM
What it means
Modbus/VERSA error code: Manual Hi-Limit from PIM.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
E68 Modbus/VERSA error code: Blower Loss from Tach Signal
What it means
Modbus/VERSA error code: Blower Loss from Tach Signal.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
E69 Modbus/VERSA error code: Flame Loss Warning
What it means
Modbus/VERSA error code: Flame Loss Warning.
What to check, in order
The manufacturer lists no fix steps for this message; it reports a state of the equipment. If it does not clear by itself, see when to call a pro below.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 85. maker's manual (PDF)
PIM red LED 6 flashes Vent Temperature Fault
Display shows: Red LED – 6 Flashes
What it means
Vent Temperature Fault.
Common causes
- High vent temperature
- Blocked flue
- Vent sensor or wiring
- Vent connections / vent system
What to check, in order
- Check for a blocked flue (if a vent sensor is fitted).
- Check the vent sensor and wiring
- Check vent connections and vent system
- If damage is observed, contact a qualified installer to inspect and repair the vent system
When to call a pro: Simple checks (power, water flow, filter, valves and settings) are fine to do yourself. Anything involving wiring or venting / flue is a job for a qualified technician.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 68. maker's manual (PDF)
ID CARD Invalid/missing ID card (3-sec delay)
What it means
Invalid/missing ID card (3-sec delay).
Common causes
- ID card invalid or missing
What to check, in order
- Connect the ID card mounted in the heater
- If 'Invalid ID Card' is reported, contact the factory.
When to call a pro: If these checks do not clear it, or the code keeps coming back, have a pool technician look at the equipment.
Applies to: VERSA IC, Hi Delta, MVB, XTherm, XVers, XFiire, IFire
Source: the Raypak control installation & operation manual (P/N 241493 Rev. 18), page 70. maker's manual (PDF)
Blue knows every code and the manual for your exact model
Ask Blue free in the Pool AI app: tell Blue the code and your model, and get the steps for your equipment.
Ask Blue freePool company? Give your techs Blue: every code, every manual and your customers' equipment in one app.
Questions
What does Raypak code PIM red LED steady on, green power LED off mean on VERSA IC boiler control?
ID Card Fault. First check: Make sure the correct ID card is firmly plugged in.
What does Raypak code PIM red LED steady on mean on VERSA IC boiler control?
Internal Control Fault. First check: Perform a power and system reset.
What does Raypak code PIM red LED 1 flash mean on VERSA IC boiler control?
Airflow Fault. First check: Check blower operation and air flow switch.
What does Raypak code PIM red LED 2 flashes mean on VERSA IC boiler control?
False Flame Error. First check: Check for proper gas valve closure.
What does Raypak code PIM red LED 3 flashes mean on VERSA IC boiler control?
Ignition Lockout Fault. First check: Check the gas supply.
Related
- Raypak Digital pool heaters 206A–407A
- Raypak Low NOx pool heaters 207A–407A
- Raypak Atmospheric heaters 268A & 408A
- Raypak Avia heaters (264 & 404)
- Raypak Above-ground heaters 106 & 156
- Raypak X94 Professional SR-410 heater
- Raypak MVB commercial heaters & boilers (504A–2004A)
- Raypak XTherm commercial heaters & boilers
- Raypak ELS electric pool & spa heaters
- All Raypak error codes
- All pool equipment error codes
General information from the manufacturers' manuals, written in our own words. Pool AI is not affiliated with or endorsed by the brands named here; brand and model names belong to their owners. Always follow the manual for your exact model and your local codes. Work on gas, high voltage and refrigerant only by qualified, licensed people. Updated 2026-11-23.